66
Class 0x05 Instance 2 attribute (Polled I/O connection)
Class 0x05 Instance 2
Attribute
ID
Access
Name
Data
type
No. of
data bytes
Range
Definition
1
Get
State
USINT
1
00
Non-existent
01
Configuring
03
Established
04
Timed out
2
Get
Instance Type
USINT
1
01
Polled I/O connection
3
Get
Transport Trigger
class
BYTE
1
00 to 0xFF
0x82: Server Transport Class 2
4
Get
Produced
Connection ID
UINT
2
0 to 0xFFFF
CAN ID that the inverter sends
5
Get
Consumed
Connection ID
UINT
2
0 to 0xFFFF
CAN ID that the inverter receives
6
Get
Initial Command
Characteristics
BYTE
1
00 to 0xFF
Source: Group 1 Message
Destination: Group 2 Message
7
Get
Produced
Connection Size
UINT
2
0 to 0xFFFF
Number of bytes of I/O data transmittable
4: Assembly Instance 70, 71
6: Assembly Instance 176
8: Assembly Instance 177
8
Get
Consumed
Connection Size
UINT
2
0 to 0xFFFF
Number of bytes of I/O data receivable
4: Assembly Instance 20, 21
6: Assembly Instance 126
8: Assembly Instance 127
9
Get/Set
Expected Packet
Rate (EPR)
UINT
2
0 to 0xFFFF
(Example) 2500: 2500 ms