78
8.4 Programming example for monitoring the output frequency
The following explains a program to read monitor functions of the inverter.
The following program reads the output frequency of station 1 inverter to D1.
Output frequency read code: H0001 (hexadecimal)
For the monitor codes, refer to
(Example) The output frequency of 60 Hz is indicated as H1770 (6000).
SB49
Set monitor code (H01) of output frequency
to RWw26.
MOV H1
W126
Turn on the monitor command (RY20)
MOV W26 D1
Read output frequency (RWr26) to D1
when the monitoring (RX20) turns on.
END
11
3
0
X1020
M0
X20
Y1020
Check the data link status of the station 1
M0
SW0B0.0