61
7
RWr10,
RWr12,
RWr14,
RWr16,
RWr18,
RWr1A
Reply code
When "1" is set in RY25, the following reply codes corresponding to the instruction code RWw10, 12,
14, 16, 18, and 1A are set. The setting value "0" is set normally, and a value other than "0" is set at an
error.
RWr11,
RWr13,
RWr15,
RWr17,
RWr19,
RWr1B
Read data
For a normal reply, the reply data to the instruction specified by the instruction code is set.
RWr20
Error status
The setting value "0" is set during normal inverter operation, and the data code of the corresponding
error is set at an error. (For the data codes or details of fault records, refer to the Instruction Manual
(Detailed) of the inverter.)
RWr21
Fault record
(fault data)
The data code of faults history No. specified by RWw21 is stored in the lower 8bits.
Lower 8 bits of RWw21 will be reverted back to the upper 8 bits.
RWr22
Fault record
(output frequency)
Output frequency of the faults history No. specified in RWw21 is stored.
RWr23
Fault record
(output current)
Output current of the faults history No. specified in RWw21 is stored.
RWr24
Fault record
(output voltage)
Output voltage of the faults history No. specified in RWw21 is stored.
Device
No.
Signal
Description
Value
Description
H0000
Normal
H0001
Write mode fault
H0002
Parameter selection fault
H0003
Setting range fault