Protective functions
Causes and corrective actions
FR-A800
6 - 19
6.5.4 Fault
When a protective function activates, the inverter trips and a fault signal is output.
Operation panel
indication
E.OC1
FR-LU-08
OC During Acc
Name
Overcurrent trip during acceleration
Description
When the inverter output current reaches or exceeds approximately 235%
of the rated current
during acceleration, the protection circuit is activated and the inverter trips.
Check point
앫
Check for sudden speed acceleration.
앫
Check if the downward acceleration time is too long in a lift application.
앫
Check for output short-circuit.
앫
Check that the Pr. 3 "Base frequency" setting is not 60 Hz when the motor rated frequency is
50 Hz.
앫
Check if the stall prevention operation level is set too high. Check if the fast-response
current limit operation is disabled.
앫
Check that the regenerative driving is not performed frequently. (Check if the output
voltage becomes larger than the V/F reference voltage at regenerative driving and
overcurrent occurs due to increase in the motor current.)
앫
Check that the power supply for RS-485 terminal is not shorted (under vector control).
앫
Check that the encoder wiring and the specifications (encoder power supply, resolution,
differential/complementary) are correct. Check also that the motor wiring (U, V, W) is correct
(under vector control).
앫
Check that the rotation direction is not switched from forward to reverse rotation (or from
reverse to forward) during torque control under Real sensorless vector control.
앫
Check that the inverter capacity matches with the motor capacity. (PM sensorless vector
control)
앫
Check if a start command is given to the inverter while the motor is coasting. (PM sensorless
vector control)
Corrective action
앫
Set the acceleration time longer. (Shorten the downward acceleration time of the lift.)
앫
If "E.OC1" always appears at start, disconnect the motor once and restart the inverter.
If "E.OC1" still appears, contact your sales representative.
앫
Check the wiring to make sure that output short circuit does not occur.
앫
Set 50 Hz in Pr. 3 "Base frequency". (Refer to page 5-690.)
앫
Lower the stall prevention operation level. Activate the fast-response current limit
operation. (Refer to page 5-325.)
앫
Set the base voltage (rated voltage of the motor, etc.) in Pr. 19 "Base frequency voltage".
(Refer to page 5-690.)
앫
Check RS-485 terminal connection (under vector control).
앫
Check the wiring and specifications of the encoder and the motor. Perform the setting
according to the specifications of the encoder and the motor (under vector control).
(Refer to page 2-71.)
앫
Prevent the motor from switching the rotation direction from forward to reverse (or from
reverse to forward) during torque control under Real sensorless vector control.
앫
Choose inverter and motor capacities that match. (PM sensorless vector control)
앫
Input a start command after the motor stops. Alternatively, use the automatic restart after
instantaneous power failure/flying start function. (Refer to page 5-590.) (IPM sensorless
vector control)
Differs according to ratings. The rating can be changed using Pr. 570 "Multiple rating setting". (Refer to page 5-209.)
148% for SLD rating,170% for LD rating, 235% for ND rating (initial setting), and 280% for HD rating
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......