Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 373
5.11.7 Output
frequency
detection
The inverter output frequency is detected and output as output signals.
Output up-to-frequency sensitivity (SU signal, Pr. 41)
●
Up to frequency (SU) is output when the output frequency reaches the set frequency.
●
The Pr. 41 value can be adjusted within the range ±1% to ±100% considering the set frequency
as 100%.
●
This parameter can be used to check that the set frequency has been reached, and provide signals
such as the operation start signal for related equipment.
Pr.
Name
Initial value
Setting range Description
FM
CA
41
M441
Up-to-frequency
sensitivity
10%
0 to 100%
Set the level where the SU signal turns ON.
42
M442
Output frequency
detection
6 Hz
0 to 590 Hz
Set the frequency where the FU (FB) signal turns
ON.
43
M443
Output frequency
detection for reverse
rotation
9999
0 to 590 Hz
Set the frequency where the FU (FB) signal turns
ON in reverse rotation.
9999
Same as the Pr. 42 setting.
50
M444
Second output frequency
detection
30 Hz
0 to 590 Hz
Set the frequency where the FU2 (FB2) signal
turns ON.
116
M445
Third output frequency
detection
60 Hz 50 Hz
0 to 590 Hz
Set the frequency where the FU3 (FB3) signal
turns ON.
865
M446
Low speed detection
1.5 Hz
0 to 590 Hz
Set the frequency where the LS signal turns ON.
870
M400
Speed detection
hysteresis
0 Hz
0 to 5 Hz
Set the hysteresis width for the detected
frequency.
Fig. 5-170:
Output of the SU signal
I002626E
SU
Set frequency
Adjustment
range Pr. 41
Time
OFF
OFF
ON
Output fr
e
q
uenc
y
(H
z)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......