Real sensorless vector control, vector control, PM sensorless vector control adjustment
Parameters
5 - 186
5.6
Real sensorless vector control, vector control,
PM sensorless vector control adjustment
5.6.1
Speed detection filter and torque detection filter
Set the time constant of primary delay filter for speed feedback signal and torque feedback signal.
Speed loop response is reduced. Under ordinary circumstances, therefore, use the initial value as it is.
These parameters are available when a vector control compatible option is installed.
Stabilizing speed detection (Pr. 823, Pr. 833)
●
Speed loop response is reduced. Under ordinary circumstances, therefore, use the initial value as
it is.
If there is speed ripple due to high frequency disturbance, adjust until speed stabilizes by
gradually raising the setting. Speed is oppositely destabilized if the setting value is too large.
●
This setting is valid under vector control only.
Stabilizing torque detection (Pr. 827, Pr. 837)
●
Current loop response is reduced. Under ordinary circumstances, therefore, use the initial value
as it is.
If there is torque ripple due to high frequency disturbance, adjust until speed stabilizes by
gradually raising the setting. Speed is oppositely destabilized if the setting value is too large.
Employing multiple primary delay filters
●
Use Pr. 833, Pr. 837 if changing filter according to application. Pr. 833, Pr. 837: Second function
selection (RT) signal
Purpose
Parameter to set
Refer
to
page
To stabilize speed and torque feedback
signal.
Speed detection filter
Torque detection filter
P.G215, P.G216,
P.G315, P.G316
Pr. 823, Pr. 827, Pr.
833, Pr. 837
To changes excitation ratio
Excitation ratio
P.G217
Pr. 854
Pr.
Name
Initial
value
Setting
range
Description
823
Speed detection filter 1
0.001 s
0
Without filter
0.001 to 0.1 s
Set the time constant of primary delay filter for speed
feedback signal.
827
G216
Torque detection filter 1
0 s
0
Without filter
0.001 to 0.1 s
Set the time constant of primary delay filter torque
feedback signal.
833
Speed detection filter 2
9999
0 to 0.1 s
Second function of Pr. 823 (enabled when RT signal
ON)
9999
Same as Pr. 823 setting
837
G316
Torque detection filter 2
9999
0 to 0.1 s
Second function of Pr. 827 (enabled when RT signal
ON)
9999
Same as Pr. 827 setting
NOTES
The RT signal is a second function selection signal. The RT signal also enables other second func-
tions. (Refer to page 5-428.)
The RT signal is assigned to the terminal RT in the initial setting. Set "3" in any of Pr. 178 to Pr. 189
(input terminal function selection) to assign the RT signal to another terminal.
Sensorless
Sensorless
Sensorless Vector
Vector
Vector
PM
PM
PM
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......