127
8
8.4.10 (Index 605Ah) Quick_stop_option_code
<Detail>
Select the operation for when Quick stop function is executed.
Abort code 0609 0030 is returned when 3, 4, 7, or 8 is written.
Sub Index
Item
Description
00h
Name
Quick_stop_option_code
Data Type
INTEGER16 (16 bit signed)
Default value
2
Unit
Access attribute
Read / Write
Availability of mapping to PDO Disable
Value
Description
Remarks
-1 ··· -32768
Manufacturer specific
0
Disable drive function
Output shutoff
1
Slow down on slow down ramp Decelerate to stop along the slope of vl_velocity_deceleration
2
Slow down on quick stop ramp Decelerate to stop along the slope of vl_velocity_quick_stop
3
4
5
Slow down on slow down ramp
and stay in QUICK STOP
Decelerate to stop along the slope of vl_velocity_deceleration
(The status transition remains Quick stop activ even after quick stop completion)
6
Slow down on quick stop ramp
and stay in QUICK STOP
Decelerate to stop along the slope of vl_velocity_quick_stop
(The status transition remains Quick stop activ even after quick stop completion)
7
8
9 ··· 32767
Reserved
A7NCA.book 127 ページ 2006年7月3日 月曜日 午前9時48分