Parameter
Adjust the output torque of the motor (current)
FR-A700 EC
6 - 147
6.7
Adjust the output torque of the motor (current)
6.7.1
Manual torque boost (Pr. 0, Pr. 46, Pr. 112)
You can compensate for a voltage drop in the low-frequency region to improve motor torque
reduction in the lowspeed range.
Motor torque in the low-frequency range can be adjusted to the load to increase the starting
motor torque.
Three types of starting torque boost can be changed by switching terminals.
Purpose
Parameter that should be Set
Refer to
Section
Set starting torque manually
Manual torque boost
Pr. 0, Pr. 46,
Pr. 112
Automatically control output current
according to load
Advanced magnetic flux vector control
Pr. 71, Pr. 80,
Pr. 81, Pr. 89,
Pr. 450, Pr. 451,
Pr. 453, Pr. 454,
Pr. 569, Pr. 800
Compensate for motor slip to secure
low-speed torque
Slip compensation
Pr. 245–Pr. 247
Limit output current to prevent
inverter trip
Stall prevention operation
Pr. 22, Pr. 23,
Pr. 66, Pr. 154,
Pr. 156, Pr. 157
Change the overload current rating
specifications
Multiple rating setting
Pr. 570
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
0
Torque boost
00023/
00038
6%
0–30%
Set the output voltage at
0Hz as %.
3
19
71
178–189
Base frequency
Base frequency
voltage
Applied motor
Input terminal
function selection
00052
to
00126
4%
00170/
00250
3%
00310
to
01800
2%
01800
or
größer
1%
46
Second torque boost
9999
0–30%
Set the torque boost value when
the RT signal is on.
9999
Without second torque boost
112
Third torque boost
9999
0–30%
Set the torque boost value when
the X9 signal is on.
9999
Without third torque boost
V/F
V/F
V/F
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......