Wiring
Electromagnetic compatibility (EMC)
FR-A700 EC
3 - 65
3.9.4
Power supply harmonics
The inverter may generate power supply harmonics from its converter circuit to affect the power
generator, power capacitor etc. Power supply harmonics are different from noise and leakage
currents in source, frequency band and transmission path. Take the following countermeasure
suppression techniques.
●
Measures
The harmonic current generated from the inverter to the input side differs according to
various conditions such as the wiring impedance, whether a reactor is used or not, and
output frequency and output current on the load side.
For the output frequency and output current, we understand that they should be calculated
in the conditions under the rated load at the maximum operating frequency.
Item
Harmonics
Noise
Frequency
Maximum 50 (
≤
3kHz)
Several 10kHz to 1GHz
Environment
To electric channel, power impedance
To-space, distance, wiring path
Quantitative understanding
Theoretical calculation possible
Random occurrence, quantitative
grasping difficult
Generated amount
Nearly proportional to load capacity
Depending on the current fluctuation
ratio (larger as switching is faster)
Affected equipment immunity
Specified in standard per equipment
Different depending on maker's equip-
ment specifications
Suppression example
Provide reactor
Increase distance
Tab. 3-29:
Differences between harmonics and noises
I001051E
Fig. 3-52:
Reduction of power supply harmonics
b
CAUTION:
The power factor improving capacitor and surge suppressor on the inverter output
side may be overheated or damaged by the harmonic components of the inverter
output. Also, since an excessive current flows in the inverter to activate over current
protection, do not provide a capacitor and surge suppressor on the inverter output
side when the motor is driven by the inverter. For power factor improvement, install
a reactor on the inverter input side or in the DC circuit.
Power
supply
AC reactor
(FR-BAL-B)
DC reactor
(FR-HEL)
M
3~
Inverter
Do not insert power
factor improving capacitor
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......