Graphic Operation Terminal F930GOT
Changeover of Display Screen (FX-PCS-DU/WIN-E) 10
10-9
10.4
Screen changeover from PLC
From the PLC, the display screen can be changed over using bit devices and word devices
(data registers).
10.4.1
Screen changeover using bit devices
This paragraph describes the method to display a specified screen when a bit device (X, Y, M,
S, T or C) becomes ON or OFF.
Set item
Description
Control Input
Do not enter any touch key.
Bit Device
Make "Bit Device" effective with a check mark, and enter a desired bit device (X, Y,
M, S, T or C).
In "Active when", select "On" (a contact) or "Off" (b contact).
Screen No.
Enter the screen No. of a screen to be displayed next among user screens (Nos. 0
to 499) and system screens (Nos. 1000 to 1030).