GOT-F900 SERIES (CONNECTION)
Connection of FREQROL (S500/E500/A500) Inverter 13
13-10
13.3.4
Specification of Station Number in Creating Screen
An inverter can be selected out of multiple units concurrently used by setting the station number under
numerical setting in screen creation for GOT-F900.
The station number specified in the screen creation software corresponds to the station number
specified for the parameter in an inverter.
There are a direct and an indirect methods to specify the station number when creating a screen.
If an individual screen is created for each inverter, it is a direct specification. Only one number
corresponding to the inverter can be selected on one screen in order to edit its numerical value.
If one screen is created for selecting an unit out of multiple inverters to edit its value, it is an indirect
specification. It is more effective in screen creation because the inverter of which the numerical value is
to be changed can be selected on one screen using the GOT-F900 internal data register (GD).
1) Direct specification
When setting the device, specify the station number of the inverter of which data is to be changed.
Setting range: 0 to 31
2) Indirect specification
When setting the device, indirectly specify the station number of the inverter of which data is to be
changed using the 16-bit GOT internal data register (GD100 to GD115).
Setting range: 100 to 115 (Corresponds to each devive from GD100 to GD115)
Setting example
a) Set the GOT internal data register (GD100) as the station number under numerical setting in the
screen creation software. (Upper)
b) Specify the device of the parameter in the inverter of which numerical value is to be displayed or
edited as follows:
PG0 (parameter) for Device, 100 for Station number (Middle)
Pr0 (parameter) for Device, 100 for Station number (Lower)
c) The parameter (PG0 and Pr0) of the inverter with the station number corresponding to GD100 is
displayed.
Screen on GOT-F900
STATION NUMBER ###
PROGRAM OPERATION ###
PARAMETER DISPLAY ###
When setting GD100
Numbers are specified where ### are indicated.
PG0:100
Pr0:100
Indicate GD100
Summary of Contents for F920GOT-BBD-K-E
Page 4: ...GOT F900 SERIES CONNECTION ii ...
Page 6: ...GOT F900 SERIES CONNECTION iv ...
Page 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Page 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Page 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Page 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Page 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Page 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Page 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Page 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Page 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Page 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Page 591: ......