Upper and lower limit settings [Defaults: Upper limit setting = Max. setting Lower limit setting = Min. setting]
The upper and lower limits can be set for each circuit as shown below. The upper and lower limits can be set only on the display unit. They
cannot be set by CC-Link communication.
◆
Current demand upper/lower limit settings
Rated primary current setting
Min. upper/lower limit setting
Setting step
Max. upper/lower limit setting
5A to 30A
0.00A
0.01A
40A to 300A
0.0A
0.1A
400A to 3000A
0A
1A
4000A to 30000A
0A
10A
Rated primary current setting
◆
Voltage upper/lower limit setting
Rated primary voltage setting
Min. upper/lower limit setting
Setting step
Max. upper/lower limit setting
110 V to 220 V
0.0 V
0.1 V
440 V to 2200 V
0 V
1 V
3300 V to 110000 V
0 V
10 V
Rated primary voltage setting
×
(15/11)
◆
Power demand upper/lower limit setting
Full-load power (kW)
Min. upper/lower limit
setting
Setting step
Max. upper/lower limit setting
Less than 12
0.000 kW
0.001 kW
12 to less than 120
0.00 kW
0.01 kW
120 to less than 1200
0.0 kW
0.1 kW
1200 to less than 12000
0 kW
1 kW
12000 to less than 120000
0 kW
10 kW
120000 or over
0 kW
100 kW
Full-load power
◆
Power factor upper/lower limit setting
Min. upper/lower limit
setting
Setting step
Max. upper/lower limit
setting
LEAD 0.50
0.05
LAG 0.50
◆
Alarm delay time [Default: 10 sec]
The setting is applied to all upper/lower limit alarms.
Setting value
0, 5 sec, 10 sec, 20 sec, 30 sec, 40 sec, 50 sec, 1 to 5 min (in 1-min steps)