60
No SYSTEM AND INSTALLATION STATUS
REMARKS
NOTES
1 INSTALLATION
LOCATION
OUTDOOR UNIT
INDOOR UNIT
2 MAINTENANCE AND ACCESS
TO REMOVE COVERS
OUTDOOR UNIT
GOOD
POOR
CYLINDER/ INDOOR UNIT
GOOD
POOR
3
SPACE AVAILABLE FOR AIR FLOW OUTDOOR UNIT
GOOD
POOR
4
TOTAL PIPING LENGTH
OUTDOOR TO INDOOR
M
5
HEIGHT DIFFERENCE
OUTDOOR TO INDOOR
M
6
STANDARD OF PIPEWORK
GOOD
POOR
7
STANDARD OF INSULATION
GOOD
POOR
8
STANDARD OF ELECTICAL INSTALLATION
GOOD
POOR
9
ACCESS TO REMOVE ELECTRICAL COVERS
GOOD
POOR
10 CONNECTION OF MAINS
POWER SOURCE
OUTDOOR UNIT
ELECTRIC CABLE
GOOD
POOR
W50-16A/ 1.6mm
W85-25A/ 4mm
HW140-40A/ 6mm
TYPE
SIZE
INDOOR UNITS
ELECTRIC CABLE
GOOD
POOR
TYPE
SIZE
11 CONNECTION OF
CONTROL WIRING
OUTDOOR
GOOD
POOR
INDOOR
GOOD
POOR
CABLE TYPE 1.5mm 3 CORE
YES
12 CONNECTION OF OPTIONS
GOOD
POOR
13 ANTI-FREEZES ADDED TO SYSTEM (25% CONCENTRATION)
YES
14 CHECK AIR CHARGE IS IN EXPANSION VESSELS
YES
15 PRESSURISE PRIMARY CIRCUIT TO APPROXIMATELY 1.50 BAR
YES
16 RELEASE AIR FROM SYSTEM
YES
OUTDOOR UNIT OPERATION STATUS
17 OUTDOOR UNIT MODEL No.
SERIAL No.
18 POWER SOURCE (v)
L-N
L-E
E-N
19 VIBRATION / NOISE
COMPRESSOR
GOOD
POOR
FAN
GOOD
POOR
20 UNIT MOUNTED ON ANTI-VIBRATION
(TICO) PADS AND SECURELY FIXED
YES
21 PROVISIONS MADE FOR
CONDENSATE REMOVEABLE
YES
NOTE:
IF POOR OS ANSWERED TO ANY OF THE ABOVE IT SHOULD BE RECTIFIED DURING THE COMMISSSIONING STAGE
NOTES AND COMMENTS
Pre-Commissioning System and Installation Check List
ENGINEERS FORMS
Table 3.5
61