82
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Parameters
Default setting Field
setting Notes
Setting
Initial settings Language
EN/FR/DE/SV/ES/IT/DA/NL/FI/NO/PT/BG/PL/CZ/RU/
TR/SL
EN
°C/°F
°C/°F
°C
Summer time
On/Off
Off
Temp. display
Room/DHW tank/Room&DHW tank /Off
Off
Time display
hh:mm/hh:mm AM/AM hh:mm
hh:mm
Room sensor settings for Zone1
TH1/Main RC/Room RC1-8/“Time/Zone”
TH1
Room sensor settings for Zone2 *2
TH1/Main RC/Room RC1-8/“Time/Zone”
TH1
Room RC zone select *2
Zone1/Zone2
Zone1
Service menu Thermistor adjustment
THW1
−10°C
to
+10°C
0°C
THW2
−10°C
to
+10°C
0°C
THW5B
−10°C
to
+10°C
0°C
THW6
−10°C
to
+10°C
0°C
THW7
−10°C
to
+10°C
0°C
THW8
−10°C
to
+10°C
0°C
THW9
−10°C
to
+10°C
0°C
THW10
−10°C
to
+10°C
0°C
THWB1
−10°C
to
+10°C
0°C
Auxiliary settings
Economy settings
for pump.
On/Off *11
On
Delay (3
to
60 min)
10 min
Electric heater
(Heating)
Space heating: On (used)/Off (not used)
On
Electric heater delay timer (5
to
180 min)
30 min
Electric heater
(DHW) *4
Booster heater
DHW: On (used)/Off (not used)
On
Immersion heater
DHW: On (used)/Off (not used)
On
Electric heater delay timer (15
to
30 min)
15 min
Mixing valve control Running (10
to
240 sec)
120 sec
Interval (1
to
30 min)
2 min
Flow sensor *12
Minimum (0
to
100 L/min)
5 L/min
Maximum (0
to
100 L/min)
100 L/min
Analog output
Interval (1
to
30 min)
5 min
Priority (Normal/High)
Normal
Pump speed
DHW
Pump speed (1
to
5)
5
Heating/Cooling
Pump speed (1
to
5)
5
Heat source setting
Standard/Heater/Boiler/Hybrid *13
Standard
Heat pump setting
Heat pump flow rate range
Minimum (0
to
100 L/min)
5 L/min
Maximum (0
to
100 L/min)
100 L/min
Quiet mode
Day (Mon
to
Sun)
—
Time
0:00 - 23:45
Quiet level (Normal/ Level1/ Level2)
Normal
Operation
settings
Heating
operation
Flow temp.range
*14
Min.temp.(20
to
45°C)
30°C
Max.temp.(35
to
60°C)
50°C
Room temp.
control
*15
Mode(Normal/Fast)
Normal
Interval(10
to
60 min)
10 min
Heat pump thermo
diff.adjust
On/Off *11
On
Lower limit (−9
to
−1°C)
−5°C
Upper limit (+3
to
+5°C)
5°C
Freeze stat function *16
Outdoor ambient temp. (3
to
20°C) / **
5°C
Simultaneous operation (DHW/
Heating)
On/Off *11
Off
Outdoor ambient temp. (−30
to
+10°C) *8
−15°C
Cold weather function
On/Off *11
Off
Outdoor ambient temp. (−30
to
−10°C) *8
−15°C
Boiler operation
Hybrid settings Outdoor ambient temp.
(−30
to
+10°C) *8
−15°C
Priority mode
(Ambient/Cost/CO
2) *17
Ambient
Outdoor ambient temp. rise
(+1
to
+5 °C)
+3 °C
Intelligent
settings
Energy
price
*18
Electricity (0.001
to
999 */kWh)
0.5
*/kWh
Boiler (0.001
to
999 */kWh)
0.5
*/kWh
CO
2
emis-
sion
Electricity
(0.001
to
999 kg -CO
2
/kWh)
0.5 kg -CO
2
/
kWh
Boiler
(0.001
to
999 kg -CO
2
/kWh)
0.5 kg -CO
2
/
kWh
Heat
source
Heat pump capacity
(1
to
40 kW)
11.2 kW
Boiler efficiency
(25
to
150%)
80%
Booster heater 1 capacity
(0
to
30 kW)
2 kW
Booster heater 2 capacity
(0
to
30 kW)
4 kW
(Continued to next page.)