![Mitsubishi Electric E1151 Installation Manual Download Page 13](http://html.mh-extra.com/html/mitsubishi-electric/e1151/e1151_installation-manual_238477013.webp)
Technical Data
Mitsubishi Electric, MA00780C
13
3
Technical Data
Parameter
E1151
Front panel, W x H x D 398 x 304 x 6 mm
Mounting depth
60 mm (160 mm including clearance)
Front panel seal
IP 66
Rear panel seal
IP 20
Keyboard material/
Front panel
Touch screen: Polyester on glass, 1 million finger touch
operations. Overlay: Autotex F157 or F207 *.
Reverse side material
Powder-coated aluminum
Weight
3.7 kg
Serial port RS422/
RS485
25-pin D-sub contact, chassis-mounted female with
standard locking screws 4-40 UNC.
Serial port RS232C
9-pin D-sub contact, male with standard locking screws 4-40
UNC.
Ethernet
Shielded RJ 45
USB
Host type A (USB 1.1), max output current 500mA
Device type B (USB 1.1)
CF-slot
Compact flash, type I and II
Flash memory for
application
12 MB (incl. fonts)
Real time clock
±20 PPM + error because of ambient temperature and supply
voltage. Total maximum error: 1 min/month at 25
°
C
Temperature coefficient: 0.004 ppm/
°
C
2
Real time clock
battery
CR2450 (UL and cUL: Sanyo or Panasonic)
Minimum lifetime: 3 years
Power consumption at
rated voltage
Normal: 1.2 A
Maximum: 1.7 A
Display
TFT-LCD. 1024 x 768 pixels, 64K color.
CCFL backlight lifetime at the ambient temperature of
+25
°
C: >35,000 h.
Active area of display,
W x H
304.1 x 228.1 mm
Fuse
Internal DC fuse, 3.15 AT, 5 x 20 mm
Power supply
+24V DC (20 - 30V DC). Power supply connector.
CE: The power supply must conform with the requirements
according to IEC 60950 and IEC 61558-2-4.
UL and cUL: The power supply must conform with the
requirements for class II power supplies.
Ambient temperature
Vertical installation: 0
°
to +50
°
C
Horizontal installation: 0
°
to +40
°
C
Storage temperature
-20
°
to +70
°
C
Relative humidity
5 - 85 % non-condensed
CE approvals
Noise tested according to EN61000-6-4 emission and
EN61000-6-2 immunity.
UL, cUL approvals
(when procuct or
packing is marked)
UL 1604 Class I, Div 2 / UL 508 / UL 50 4x indoor use only
DNV
Yes
NEMA
4x indoor use only
* See section
Chemical Resistance
for more information.
Summary of Contents for E1151