. Combination of outdoor units
Component units of PURY-P144 to P240 are listed below.
Outdoor unit model
Component unit model
PURY-P72THMU-A(-BS)
-
-
PURY-P96THMU-A(-BS)
-
-
PURY-P120THMU-A(-BS)
-
-
PURY-P144TSHMU-A(-BS)
PURY-P72THMU-A(-BS)
PURY-P72THMU-A(-BS)
PURY-P168TSHMU-A(-BS)
PURY-P96THMU-A(-BS)
PURY-P72THMU-A(-BS)
PURY-P192TSHMU-A(-BS)
PURY-P96THMU-A(-BS)
PURY-P96THMU-A(-BS)
PURY-P216TSHMU-A(-BS)
PURY-P120THMU-A(-BS)
PURY-P96THMU-A(-BS)
PURY-P240TSHMU-A(-BS)
PURY-P120THMU-A(-BS)
PURY-P120THMU-A(-BS)
Component units of PURY-P144 to P240 are listed below.
Outdoor unit model
Component unit model
PURY-P72YHMU-A(-BS)
-
-
PURY-P96YHMU-A(-BS)
-
-
PURY-P120YHMU-A(-BS)
-
-
PURY-P144YSHMU-A(-BS)
PURY-P72YHMU-A(-BS)
PURY-P72YHMU-A(-BS)
PURY-P168YSHMU-A(-BS)
PURY-P96YHMU-A(-BS)
PURY-P72YHMU-A(-BS)
PURY-P192YSHMU-A(-BS)
PURY-P96YHMU-A(-BS)
PURY-P96YHMU-A(-BS)
PURY-P216YSHMU-A(-BS)
PURY-P120YHMU-A(-BS)
PURY-P96YHMU-A(-BS)
PURY-P240YSHMU-A(-BS)
PURY-P120YHMU-A(-BS)
PURY-P120YHMU-A(-BS)
4. Specifications
Model
PURY-P72THMU-A(-BS) PURY-P96THMU-A(-BS) PURY-P120THMU-A(-BS) PURY-P144TSHMU-A(-BS) PURY-P168TSHMU-A(-BS) PURY-P192TSHMU-A(-BS) PURY-P216TSHMU-A(-BS) PURY-P240TSHMU-A(-BS)
Sound level (60Hz)
58dB<A>
58dB<A>
60dB<A>
61dB<A>
61dB<A>
62dB<A>
62dB<A>
63dB<A>
External static pressure
0 Pa *2
Indoor
units
Total capacity
50 ~ 150% *1
Model
06 ~ 96
Quantity
1 ~ 18
1 ~ 24
1 ~ 30
1 ~ 36
1 ~ 42
1 ~ 48
2 ~ 50*
2 ~ 50*
Operation
temperature
Standard type
Cooling mode: −5°CDB ~ 43°CDB [23°FDB ~ 109°FDB]
Heating mode: −20°CWB ~ 15.5°CWB [−4°FWB ~ 60°FWB]
Outside air
intake type
Cooling mode: 21°CDB/15.5°CWB ~ 43°CDB/35°CWB [70°FDB/60°FWB ~ 109°FDB/95°FWB]
Heating mode: −12.5°CWB ~ 20°CWB [−9.5°FWB ~ 68°FWB]
Model
PURY-P72YHMU-A(-BS) PURY-P96YHMU-A(-BS) PURY-P120YHMU-A(-BS) PURY-P144YSHMU-A(-BS) PURY-P168YSHMU-A(-BS) PURY-P192YSHMU-A(-BS) PURY-P216YSHMU-A(-BS) PURY-P240YSHMU-A(-BS)
Sound level (60Hz)
58dB<A>
58dB<A>
60dB<A>
61dB<A>
61dB<A>
62dB<A>
62dB<A>
63dB<A>
External static pressure
0 Pa *2
Indoor
units
Total capacity
50 ~ 150% *1
Model
06 ~ 96
Quantity
1 ~ 18
1 ~ 24
1 ~ 30
1 ~ 36
1 ~ 42
1 ~ 48
2 ~ 50*
2 ~ 50*
Operation
temperature
Standard type
Cooling mode: −5°CDB ~ 43°CDB [23°FDB ~ 109°FDB]
Heating mode: −20°CWB ~ 15.5°CWB [−4°FWB ~ 60°FWB]
Outside air
intake type
Cooling mode: 21°CDB/15.5°CWB ~ 43°CDB/35°CWB [70°FDB/60°FWB ~ 109°FDB/95°FWB]
Heating mode: −12.5°CWB ~ 20°CWB [−9.5°FWB ~ 68°FWB]
*Connectable branch pipe number is max. 48.
*1: The total indoor capacity of units run simultaneously is 150% or less.
*2: To enable high static pressure, set the DipSW on the main panel as follows.
SW3-9: ON, SW3-10 60Pa compatible: OFF, 30Pa compatible: ON