Model:
PUHY-P216TSKMU-A
(Consists of One PUHY-P120TKMU-A, One PUHY-P96TKMU-A, and One CMY-Y100CBK3 Twinning Kit)
OUTDOOR VRF HEAT PUMP SYSTEM FEATURES
•
3-phase, 208/230V
•
Modular variable refrigerant flow (VRF) systems;
smaller capacity units can be piped together to form a single,
large-capacity two-pipe system
• Required
T
winning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static pressure;
factory set to 0"WG
• Connects to CIT
Y MUL
TI indoor units; controlled via
CIT
Y MUL
TI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating
T
emperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
OPTIONAL PARTS
□
T
w
inning
K
it*.…………………………………...…….CMY-Y
1
00C
BK
3
□
T-
B
ranch Joint
(≤
72,000
B
tu/h
)
………………..........CMY-Y
1
02SS
-G2
□
T-
B
ranch Joint
(≤
144
,000
B
tu/h
)
……………….…....CMY-Y
1
02
LS-G2
□
T-
B
ranch Joint
(≤
23
4
,000
B
tu/h
)
……………….........CMY-Y202
S-G2
□
Header
(4
-
B
ranch
;
≤
72,000
B
tu/h
)
........………………CMY-Y
1
0
4C-G
□
Header
(
8-
B
ranch
;
≤
144
,000
B
tu/h
)
......………………CMY-Y
1
0
8C-G
□
Header
(1
0-
B
ranch
;
≤
23
4
,000
B
tu/h
)
....………………CMY-Y
1
0
10C-G
* T
w
inning
K
it is necessary to combine the refrigerant
fl
o
w
s of the
modules and is sold separately.
Specifications
System
Module 1
Module 2
Unit
Type
PUHY
-P216TSKMU-A
PUHY
-P120TKMU-A
PUHY
-P96TKMU-A
Nominal Cooling Capacit
y
Btu/h
216,000
120,000
96,000
Nominal Heating Capacit
y
Btu/h
243,000
135,000
108,000
External Dimensions (H x W x D
)
In. / mm
Refer to Module Data
65
x
6
8-29/32
x
29-
5
/23 /
1
,
65
0
x
1
,7
5
0
x
7
4
0
65
x
48
8
-1/16 x 29-5/32 /
1
,
65
0
x
1
,220
x
7
4
0
Net Weight
Lbs. / kg
1,220 / 557
697 / 316
532 / 241
Electrical Power Requirements
V
oltage, Phase, Hertz
R
efer to Module Data**
208 / 230V
, 3-phase, 60Hz**
Cooling Power Input
kW
16.90
Refer to System Data
Heating Power Input
kW
19.26
Cooling Current (208/230V
)
R.L.A.
52.1 / 47.1
Refer to System Data
Heating Current (208/230V
)
R.L.A.
59.4 / 53.7
Minimum Circuit
Ampacity
(MCA)**
A
R
efer to Module Data**
45 / 42**
34 / 31**
Maximum Breaker Size**
A
R
efer to Module Data**
50**
40**
Maximum Overcurrent Protection**
A
R
efer to Module Data**
73 / 67**
57 / 52**
Piping Diameter
Refer to System Data
F
rom
T
w
i
nn
i
ng
K
i
t
to
I
ndoor
U
n
i
ts
(
B
raz
e
d
)
(
I
n.
/
mm
)
Liquid (High Pressure)
5/8 / 15.88
Gas (Low Pressure)
1-1/8 / 28.58
From Modules to
T
winning Kit
(Brazed) (In. / mm)
Liquid (High Pressure)
Refer to Module Data
1/2 / 12.7
3/8 / 9.52
Gas (Low Pressure)
1-1/8 / 28.58
7/8 / 22.2
Indoor Unit
T
otal Capacity
50 to 130% of ODUs
Refer to System Data
Model / Quantity
P06 ~ P96 / 2 to 46
Sound Pressure Levels
dB(A)
62.5
60.0
58.0
Fan
Refer to Module Data
T
ype x Quantity
Propeller Fan x 2
Propeller Fan x 1
Airflow Rate
CFM
11,300
6,200
Di
r
ec
t
-
dr
i
v
e I
nv
e
rt
e
r
M
otor
O
ut
p
ut
kW
0.92 + 0.92
0.92
Compressor Operating Range
8% to 100%
Refer to System Data
Compressor
T
ype x Quantity
Refer to Module Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
Compressor Motor Output
kW
8.1
7.1
Compressor Crankcase Heater
kW
-
-
Refrigerant
Refer to Module Data
R410A
Lubricant
MEL32
High-pressure Protection Device
Refer to Module Data
601 psi / 4.15 MPa
601 psi / 4.15 MPa
Compressor / Fan Protection Device
O
verheat
P
rotection / Thermal S
w
itch
O
verheat
P
rotection / Thermal S
w
itch
Inverter Protection Device
Overheat / Overcurrent Protectio
n
Overheat / Overcurrent Protection
B
lu
e Fi
n
A
nt
i-c
orros
i
on
P
rot
ec
t
i
on
:
Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants
;
≥1μ
m thic
k;
Salt Spray Test Method - no unusual rust development to
4
80 hours.
P
UHY-
P120TKMU-A
** Each individual module re
q
uires a separate electrical connection.
R
eference electrical data for each individual module.
P
UHY-
P96TKMU-A