G
B
GB-53
KJ79F137H01
11-2. Function setting
Make function settings by setting the dipswitches SW4, SW6, and SWP3 on the main board.
Write down the switch settings on the electrical wiring diagram label on the control box front panel for future reference
when the control box needs to be replaced.
・
Take the following steps to make snow sensor settings. (Snow sensor control will not function when the outdoor
temperature sensor (TH7) reading is 6ºC (43ºF) or above.)
①
Set the 10th bit of SW6 to ON.
②
Set SW4 as shown in the table below to select the setting item No.933 or 934. (The setting item No. will be
displayed on LED1.)
③
Press SWP3 for two seconds or longer to change the settings. (The settings can be checked on LED3.)
Setting item
No.
SW4 0: OFF, 1: ON *
1
Setting (LED3 display) *
2
1
2
3
4
5
6
7
8
9
10
Unlit
Lit
Snow sensor
setting
933
1
0
1
0
0
1
0
1
1
1
No. 934 ineffective
No. 934 effective
934
0
1
1
0
0
1
0
1
1
1
Continuous fan operation
Intermittent fan operation
*1 Make the SW4 setting after the unit is energized.
*2 This will blink while the system is starting up.
・
Make various function settings by setting SW5 and SW6, referring to the table below.
Setting content
Setting
Switch setting timing
OFF
ON
SW5-1
Centralized control switch
Without connection to the
centralized controller
With connection to the
centralized controller
Before being energized
SW5-2
Deletion of connection information
Normal control
Deletion
Before being energized
SW5-3
–
Preset before shipment
–
SW5-4
–
–
SW5-5
–
–
SW5-6
–
–
SW5-7
–
–
SW5-8
–
–
Setting content
Setting
Switch setting timing
OFF
ON
SW6-1
–
–
–
–
SW6-2
–
–
–
–
SW6-3
–
–
–
–
SW6-4
High static pressure setting
Refer to *1.
Refer to *1.
Before being energized
SW6-5
SW6-6
–
–
–
–
SW6-7
Low-noise mode selection
Performance priority
Low-noise priority
Any time after being energized
SW6-8
Selection of Low-noise or Demand
Low-noise (Night)
Demand
Before being energized
SW6-9
Selection of Diagnostic display or
Function detail setting
Refer to *2.
Refer to *2.
Any time after being energized
SW6-10
* Do not change the factory settings of SW5-3 through SW5-8.
* Unless otherwise specified, leave the switch to OFF where indicated by "–," which may be set to OFF for a reason.
*1
SW6-5: ON
SW6-5: OFF
SW6-4: ON
80 Pa
60 Pa
SW6-4: OFF
30 Pa
0 Pa
*2
SW6-10: ON
SW6-10: OFF
SW6-9: ON
LED (round type) No. 0 to 1023
LED (7seg) No. 1024 to 2047
SW6-9: OFF
Function setting No. 0 to 1023
LED (7seg) No. 0 to 1023
Summary of Contents for City Multi PUHY-EP1250YSNW-A
Page 2: ......