8-2. FUNCTION OF DIP SWITCH
The black square (■) indicates a switch position.
Switch
Pole
Function
Operation by switch
Effective
timing
Remarks
ON
OFF
SW1
Function
Selection
1
Thermistor
<Room temperature
detection> position
Built-in remote
controller
Indoor unit
Under
suspension
Address board
ON
OFF
ON
OFF
1 2 3 4 5 6 7 8 9 0
<Initial setting>
*
1
Refer to <Table A> below.
2
Filter clogging detection Provided
Not provided
3
Filter cleaning
2,500 hr
100 hr
4
Fresh air intake
Effective
Not effective
5
Switching remote
display
Thermo-ON signal display Indicating fan
operation ON/OFF
6
—
—
—
7
Air flow set in case of
thermo-OFF at heating mode
Low*
1
Extra low*
1
8
Setting air flow*
1
Depends on SW1-7
9
Auto restart function Effective
Not effective
0
Power ON/OFF by breaker Effective
Not effective
SW2
Capacity
code
setting
1–6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
25
MODELS
MODELS
SW2
SW2
32
40
50
63
ON
OFF
1 2 3 4 5 6
20
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
MODELS
SW2
80
100
ON
OFF
1 2 3 4 5 6
125
Before
power
supply
ON
Indoor controller board
Set while the unit is off.
<Initial setting>
Set for each capacity.
SW3
Function
setting
1
Heat pump/Cooling only Cooling only
Heat pump
Under
suspension
Indoor controller board
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 0
*
2
Refer to <Table D> below for SW3-5
and SW-3-6.
2
—
—
—
3
3D i-see Sensor
positioning
The setting depends on the combination of
SW3-3 and SW3-4. Refer to <Table B> below.
Before power
supply ON
4
5
Vane horizontal angle
1
Second setting*
2
First setting*
2
Under
suspension
6
Vane horizontal angle
2
Third setting*
2
Depends on SW3-5
7
Changing the opening of
linear expansion valve Effective
Not effective
8
Heat 4 degrees up
Not effective
Effective
9
3D i-see Sensor
ceiling height setting
The setting depends on the combination of
SW3-9 and SW3-10. Refer to <Table C> below.
0
SW4
Model selection 1–6
In case of replacing the indoor controller board, make sure to set
the switch to the initial setting, which is shown below.
ON
OFF
1 2 3 4 5 6
Before
power
supply
ON
Indoor controller board
<Table A>
SW1-7
SW1-8
OFF
OFF
Extra low
ON
OFF
Low
OFF
ON
Setting air flow
ON
ON
stop
<Table D>
SW3-5
SW3-6
Vane setting Initial setting Setting
Vane position
OFF
OFF
Setting
1
Standard
Standard
ON
OFF
Setting
2
●
Less draft*
3
Upward position than the standard
OFF
ON
Setting
3
Less smudging Downward position than the standard
ON
ON
Unused
─
─
*
3
Be careful of the smudge on ceiling.
<Table B>
SW3-3
SW3-4
OFF
OFF
Setting
1
ON
OFF
Setting
2
OFF
ON
Setting
3
ON
ON
Setting
4
<Table C>
SW3-9 SW3-10
OFF
OFF
Low ceiling
ON
OFF
Standard
OFF
ON
High ceiling
ON
ON
(High ceiling)
Continue to the next page
OCH657