8-1. COUNTERMEASURES FOR ERROR DURING TEST RUN
If a problem occurs during test run, a code number will appear on the remote controller (or LED on the outdoor unit), and the
air conditioning system will automatically cease operating.
Refer to the connected outdoor unit service manual in order to determine the nature of the abnormality and apply corrective
measure.
Check
code
Trouble
Detected Unit
Remarks
Indoor
Outdoor
Remote
Controller
0403 Serial communication error
Outdoor unit Multi controller board ~
Power board communication trouble
1102 Compressor temperature
Check delay code 1202
1300 Low pressure
1302 High pressure
Check delay code 1402
1500 Superheat due to low discharge temperature
Check delay code 1600
1501
Refrigerant shortage
Check delay code 1601
Blocked valve in cooling mode
Check delay code 1501
1508 4-way valve trouble in heating mode
Check delay code 1608
2500 Water leakage
2502 Drain over flow protection
2503 Drain sensor abnormality
4100 Compressor current interruption (locked compressor)
Check delay code 4350
4210 Compressor overcurrent interruption
4220 Voltage shortage/overvoltage/PAM error/L1open phase/power synchronization
signal error
Check delay code 4320
4230 Heat Sink temperature
Check delay code 4330
4250 Power module
Check delay code 4350
4400 Rotational frequency of outdoor fan motor
Check delay code 4500
5101
Air inlet thermistor trouble (TH21) or
Compressor temperature thermistor (TH4) open/short
Check delay code 1202
5102
Liquid pipe temperature thermistor trouble (TH22)
Suction pipe temperature thermistor (TH6) open/short
Check delay code 1211
5103 Gas pipe temperature thermistor trouble (TH23)
5105 Outdoor liquid pipe temperature thermistor (TH3) open/short
Check delay code 1205
5106 Ambient thermistor (TH7) open/short
Check delay code 1221
5109 HIC pipe temperature thermistor (TH2) open/short
Check delay code 1222
5110 Heat Sink temperature thermistor (TH8) open/short
Check delay code 1214
5201 High pressure sensor (63HS)
Check delay code 1402
5202 Low pressure sensor (63LS)
Check delay code 1400
5701 Contact failure of drain float switch
6600 Duplex address error
Only M-NET Remote controller is detected.
6602 Transmission processor hardware error
Only M-NET Remote controller is detected.
6603 Transmission bus BUSY error
Only M-NET Remote controller is detected.
6606 Signal communication error with transmission processor
Only M-NET Remote controller is detected.
6607 No ACK error
Only M-NET Remote controller is detected. *
6608 No response frame error
Only M-NET Remote controller is detected. *
6831 MA communication receive error (no receive signal)
Only MA Remote controller is detected.
6832 MA communication send error
Only MA Remote controller is detected.
6833 MA communication send error
Only MA Remote controller is detected.
6834 MA communication receive error
Only MA Remote controller is detected.
7100 Total capacity error
7101 Capacity code error
7102 Connecting excessive number of units
7105 Address setting error
Note:
When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal.
*Abnormality for PWFY series
TROUBLESHOOTING