19
Control modes
Control details
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
•
Room temperature
desired temperature -2°F ···Thermo ON
•
Room temperature
desired temperature ···Thermo OFF
1. Thermoregulating
function
Remarks
Controlled by the remote controller (3-speed)
Give priority to controlled mode mentioned below.
2-1. Hot adjust mode
2-2. Residual heat exclusion mode
2-3. Thermo OFF mode (When the compressor off by the thermoregulating)
2-4. Cool air prevention mode (Defrosting mode)
2-5. Capacity increasing mode
2-1. Hot adjust mode
The fan controller becomes the hot adjust mode for the following conditions.
When starting the HEAT operation
When the thermoregulating function changes from OFF to ON.
When release the HEAT defrosting operation
2. Fan
A: Hot adjust mode start
B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature
turned 95°F or more
C: 2 minutes have passed since the condition A (Terminating the hot adjust mode)
A
C
B
[Extra Low]
[Low]
Set fan speed by the remote controller
Hot adjust mode
+
1
2-2. Residual heat exclusion mode
When the condition changes the auxiliary heater ON to OFF (thermoregulating or
operation stop, etc), the indoor fan operates in [Low] mode for 1 minute.
This control is
same for the
model without
auxiliary heater.
+
1
"STAND BY" will
be displayed
during the hot
adjust mode.
Continued to the next page
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
ûFûC
°F °C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
9-4. HEAT OPERATION
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display HEAT.
3
Press the TEMP. button to set the desired temperature.
NOTE
: The set temperature changes 1°F(2°F) when the or button is
pressed once. Heating 63 to 83°F
Variable range of the set temprature depends on the remote controller
which is applied.
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]