background image

8

D

F

e

i

n

L

p

G

r

ru

T

r

GB

GB

GB

GB

GB

GB

5. Caring for the machine

Always have filter maintenance performed by a service person.
Before care-taking, turn the power supply OFF.

 Caution:

•  Before you start cleaning, stop operation and turn OFF the power supply. 

Remember that the fan is rotating inside at high speed, posing a serious 
risk of injury.

•  Indoor units are equipped with filters to remove the dust of sucked-in 

air. Clean the filters following the procedures on the right. (The standard 
filter should normally be cleaned once a week, and the long-life filter at 
the beginning of each season.)

•  The life of the filter depends on where the unit is installed and how it is 

operated.

How to clean

•  Clear dust away lightly or clean it up with a vacuum cleaner. In the case of 

severe staining, wash the filter in lukewarm water mixed with dissolved neutral 
detergent or water, and then rinse off the detergent completely. After washing, 
dry it and fix it back into place.

 Caution:

•  Do not dry the filter by exposing it to direct sunlight or warming it using 

fire, etc. Doing so can result in the deformation of the filter.

•  Washing it in hot water (more than 50 °C [122 °F]) can also result in de-

formation.

 Caution:

Never  pour  water  or  flammable  sprays  onto  the  air  conditioner.  Cleaning 
using these methods can result in the failure of the air conditioner, electric 
shock, or fire.

6. Troubleshooting

Before you ask for repair service, check the following points:

State of Machine

remote controller

cause

Troubleshooting

It does not run.

“ ” display is not lit up.

No  display  appears  even 

when the [ON/OFF] button 

is pressed.

Power failure

Press the [ON/OFF] button after power restoration.

The power supply is turned OFF.

Turn the power supply ON.

The fuse in the power supply is gone.

Replace fuse.

The earth leakage breaker is gone.

Put in the earth leakage breaker.

Air flows out but it does 
not cool enough or heat 
enough.

The liquid crystal display 
shows that it is in the 
state of operation.

improper temperature adjustment

After checking the set temperature and inlet temperature 
on the liquid crystal display, refer to [Room temperature 
adjustment], and operate the adjustment button.

The filter is filled with dust and dirt.

Clean up the filter.
(Refer to [Caring for the machine].)

There are some obstacles at the air inlet and outlet of 
the indoor and outdoor units.

Remove.

Windows and doors are open.

Close.

Cool air or warm air 
does not come out.

The liquid crystal display 
shows that it is in opera

-

tion.

The restart-preventing circuit is in operation for 
3 minutes.

Wait for a while.
(To protect the compressor, a 3-minute restart-preventing 
circuit is built into the indoor unit. Therefore, there are 
occasions sometimes when the compressor does not start 
running immediately. There are cases when it does not run 
for as long as 3 minutes.)

Indoor unit operation was restarted during the heating 
and defrosting operation.

Wait for a while.
(Heating operation starts after ending defrosting operation.)

It runs briefly, but soon 
stops.

The “CHECK” and check 
code flashes on the liquid 
crystal display.

There are some obstacles at the air inlet and outlet of 
the indoor and outdoor units.

rerun after removal

The filter is filled with dust and dirt.

Rerun after cleaning the filter. (Refer to [Caring for the 
machine].)

The sound of the 
exhaust and rotation 
of the motor can still 
be heard after stop of 
running.

All lights are out except 
the powered display of 
“ ”.

When other indoor units are engaged in cooling 
operation, the machine stops after running a drain-up 
mechanism for 3 minutes when air-cooling operation 
is stopped.

Wait for 3 minutes.

The sound of the 
exhaust and the rota

-

tion of the motor can 
be heard intermittently 
after stop of running.

All lights are out except 
the powered display of 
“ ”.

When other indoor units are engaged in cooling opera

-

tion, drained water is brought in. If the drain water is 
collected, the drain-up mechanism initiates a draining 
operation.

It soon stops. (If the noise occurs more than 2-3 times in 
an hour, ask for repair service.)

Warm air comes out 
intermittently when the 
thermostat is OFF or 
during fan operation.

The liquid crystal display 
shows that it is in the 
state of operation.

When other indoor units are engaged in heating op

-

eration, the control valves are opened and closed from 
time to time to maintain the stability of the system.

It soon stops. (If the room temperature rises uncomfortably 
high in a small room, stop operation.)

•  If operation stops due to a power failure, the [restart-preventing circuit at power failure] operates and disables unit operation even after power restoration. In this case, 

press the [ON/OFF] button again and start operation.

If malfunctions persist after you have checked the above, turn the power supply OFF and contact your dealer with information about the product name, the nature of the 
malfunction, etc. If the display of “[CHECK]” and (4 digit) check code flashes, tell the dealer contents of the display (check code). Never attempt to repair by yourself.

The following symptoms are not air conditioner failures:

•  The air blown out from the air conditioner can sometimes give off odors. This is due to cigarette smoke contained in the air of the room, the smell of cosmetics, the walls, 

furniture, etc., absorbed in the air conditioner.

•  A hissing noise can be heard immediately after the air conditioner is started or stopped. This is the sound of the refrigeration flowing inside the air conditioner. This is 

normal.

•  The air conditioner sometimes snaps or clicks at the beginning or end of cooling/heating operation. This is the sound of friction on the front panel and other sections 

due to expansion and contraction caused by temperature change. This is normal.

•  The fan speed changes in spite of not changing the setting. Not to blow out cold air at the beginning of heating operation, the air conditioner automatically adjusts the 

fan speed gradually from lower to the set speed. It also adjust its fan speed to protect the fan motor when return air temperature or fan speed excessively rises.

Summary of Contents for CITY MULTI PEFY-P06NMAU-E3

Page 1: ...MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte ...

Page 2: ... 1 8 400 500 15 3 4 19 11 16 1500 59 1 16 2000 78 3 4 PEFY P54NMAU E3 1600 63 500 600 19 11 16 23 5 8 1700 66 15 16 2200 86 5 8 Unit mm in G H I F 700 27 9 16 450 17 3 4 475 18 3 4 450 17 3 4 Q 50 150 2 5 15 16 450 17 3 4 450 17 3 4 100 200 3 15 16 7 7 8 Min 300 11 13 16 P E A D H G Min 20 13 16 Min 10 7 16 B C A B J P 50 2 R 777 30 5 8 450 17 3 4 475 18 3 4 700 27 9 16 50 2 Min 300 11 13 16 E A I...

Page 3: ...draining A Unit body B Lifting machine C Nuts field supply D Washers square accessory E M10 hanging bolt field supply 5 5 2 Fig 5 1 1 Fig 5 1 2 5 1 6 6 2 Fig 6 2 1 A Center of gravity A Indoor unit s bottom surface A Y X L W A Z C D C E D B A 137 5 7 16 67 2 5 8 239 9 7 16 357 14 1 16 122 4 13 16 33 1 5 16 41 1 5 8 217 8 9 16 C A B D Fig 5 2 1 Unit mm in ...

Page 4: ...as large as possible About 10 cm 3 15 16 in F Indoor unit G Make the piping size large for grouped piping H Downward slope 1 100 or more I O D ø38 mm 1 1 2 in PVC TUBE for grouped piping 9 mm 3 8 in or more insulation J Up to 700 mm 27 9 16 in N Drain hose accessory O Horizontal or slightly upgradient 7 2 Fig 7 2 2 C B A L D D D E K M B H I Max 20 m 65 ft 1 5 2 m 5 7 ft G F F F B C D D G F E H A 3...

Page 5: ... to 1 5 8 in B Remove the water supply port C About 2500 cc D Water E Filling port F Screw Fig 8 0 2 SWE Fig 7 3 2 Fig 8 0 3 Fig 8 0 4 Indoor controller board A B F C D E A B G F A C E D A B G C E A F D A B A Filter B Bottom plate C Nail for the bottom inlet D Nail for the rear inlet C D A In case of rear inlet B In case of bottom inlet A Duct B Air inlet C Access door D Canvas duct E Ceiling surf...

Page 6: ...together to the S terminal Dead end connection E Insulation tape To keep the earth wire of the shielded cable from coming in contact with the transmis sion terminal 9 3 Fig 9 3 3 Fig 9 3 4 Fig 9 3 5 C Terminal box D Knockout hole E Remove A Screw holding cover 1pc B Cover Fig 9 3 1 Fig 9 3 2 A Non polarized B TB15 C Remote Controller D TB5 Fig 9 2 3 Fig 9 2 4 2 S M2 M1 A B D 1 DC10 13V A B 1 2 L1 ...

Page 7: ...tall the accessories Improper installation by the user may result in water leakage electric shock or fire Never repair the unit If the air conditioner must be repaired consult the dealer If the unit is repaired improperly water leakage electric shock or fire may result If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to...

Page 8: ...e its parts When installing the unit in a hospital communication station or similar place provide sufficient protection against noise The inverter equipment private power generator high frequency medical equipment or radio communication equipment may cause the air conditioner to operate erroneously or fail to operate On the other hand the air conditioner may affect such equipment by creating noise...

Page 9: ...e W mm in L mm in X mm in Y mm in Z mm in Product Weight kg lb PEFY P06NMAU E3 643 25 5 16 754 29 11 16 330 13 300 11 13 16 130 5 1 8 22 49 PEFY P08NMAU E3 643 25 5 16 754 29 11 16 330 13 300 11 13 16 130 5 1 8 22 49 PEFY P12NMAU E3 643 25 5 16 754 29 11 16 330 13 300 11 13 16 130 5 1 8 22 49 PEFY P15NMAU E3 643 25 5 16 954 37 9 16 340 13 3 8 375 14 3 4 130 5 1 8 26 58 PEFY P18NMAU E3 643 25 5 16 ...

Page 10: ...or accidents resulting from the use of the wrong type of refrigerant Caution Use refrigerant piping made of C1220 Cu DHP phosphorus deoxidized copper as specified in the JIS H3300 Copper and copper alloy seamless pipes and tubes In addition be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur oxides dust dirt shaving particles oils moisture or any other co...

Page 11: ...ulation to inlet duct flange and outlet duct to prevent condensa tion Be sure to change the position of air filter to the position where it can be serv iced Fig 8 0 1 P 5 A In case of rear inlet B In case of bottom inlet A Duct B Air inlet C Access door D Canvas duct E Ceiling surface F Air outlet G Leave distance enough to prevent short cycle Procedure for changing the rear inlet to the bottom in...

Page 12: ...length 200 m Maximum length of transmission lines for centralized control and indoor outdoor transmission lines Maximum length via indoor units 500 m MAX The maximum length of the wiring between power supply unit for transmission lines on the transmission lines for centralized control and each outdoor unit and system controller is 200 m When 10 m is exceeded use cables with the same specification ...

Page 13: ...ved it cannot operate normally 9 4 External I O specifications Caution 1 Wiring should be covered by insulation tube with supplementary insula tion 2 Use relays or switches with IEC or equivalent standard 3 The electric strength between accessible parts and control circuit should have 2750 V or more 9 2 Connecting remote controller indoor and outdoor transmission cables Connect indoor unit TB5 and...

Page 14: ... varies with the system at site Set them referring to the Data Book 9 7 Sensing room temperature with the built in sensor in a remote controller If you want to sense room temperature with the built in sensor in a remote control ler set SW1 1 on the control board to ON The setting of SW1 7 and SW1 8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is...

Page 15: ...ress telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Page 16: ... F OPERATION MANUAL For safe and correct use please read this operation manual thoroughly before operating the air conditioner unit MANUEL D UTILISATION Pour une utilisation correcte sans risques veuillez lire le manuel d utilisation en entier avant de vous servir du climatiseur ...

Page 17: ...F FILTER CHECK CLEAR MENU ON OFF TEST TEMP CLOCK OPERATION BACK DAY MONITOR SET 1 2 3 4 D 5 6 8 9 C 0 A B 7 Remote controller Button Touche Commande à distance GB F 1 Touche Réglage de la température 2 Touche Timer Menu 3 Touche Mode Touche Monitor Set Touche Back 4 Touche Timer On Off 5 Touche Louvre Touche Set Day Touche Operation 6 Touche Vitesse du ventilateur 7 Touche Commande des ailettes 8 ...

Page 18: ...pièce N Réglage des ailettes O Vitesse du ventilateur P Témoin de fonctionnement Remote controller Display Affichage Commande à distance GB F A Current time Timer time B Centralized control indicator C Timer OFF indicator D Timer mode indicator E Operation mode display COOL DRY AUTO FAN HEAT F Function mode indicator G Preset temperature H Power indicator I Louver J Ventilation K Filter sign L Sen...

Page 19: ...4 4 2 In case of bottom inlet En cas d entrée sur le dessous 1 In case of rear inlet En cas d entrée arrière A Filter Filtre Air Flow Flux d air A 1 A 2 Fig A ...

Page 20: ...use of the wrong type of refrigerant 1 Outdoor unit Warning The outdoor unit must be installed on a stable level surface in a place where there is no accumulation of snow leaves or rubbish Do not stand on or place any items on the unit You may fall down or the item may fall causing injury Caution The outdoor unit should be installed in a location where air and noise emitted by the unit will not di...

Page 21: ...it consult your dealer If pipes are removed incorrectly refrigerant fluorocarbon gas may blow out and come into contact with your skin causing injury Releasing refrigerant into the atmosphere also damages the environment 2 Names and functions of various parts Attachment and detachment of filter Fig A P 4 3 How to operate Before starting operation Start running after the PLEASE WAIT display has dis...

Page 22: ...on according to the change of the room temperature and automatically repeat ON OFF 2 When reaching room temperature of your choice Both the compressor and indoor fan stop When stop continues for 10 minutes the compressor and indoor fan are oper ated for 3 minutes to keep the humidity low For heating Press the 3 Mode BACK Button to bring up the HEAT display Regarding displays during heating operati...

Page 23: ... Heating operation starts after ending defrosting operation It runs briefly but soon stops The CHECK and check code flashes on the liquid crystal display There are some obstacles at the air inlet and outlet of the indoor and outdoor units Rerun after removal The filter is filled with dust and dirt Rerun after cleaning the filter Refer to Caring for the machine The sound of the exhaust and rotation...

Page 24: ...f the professional engineering work required for transferring the instal lation Caution When moving or reinstalling the air conditioner consult with your dealer Defective installation can result in electric shock fire etc Regarding noise In installing work choose a place that can fully bear the weight of the air con ditioner and where noise and vibration can be reduced Choose a place where cool or...

Page 25: ...The operating noise is the data that was obtained in an anechoic room Item Model P36NMAU E3 P48NMAU E3 P54NMAU E3 Power source 208 230V 60Hz Cooling capacity 1 Heating capacity 1 Btu h 36 000 40 000 48 000 54 000 54 000 60 000 kW 10 6 11 7 14 1 15 8 15 8 17 6 Dimension Height mm in 250 9 13 16 Width mm in 1 400 55 1 8 1 600 63 Depth mm in 732 28 7 8 Net weight kg lb 39 86 42 93 Fan Airflow rate Lo...

Page 26: ...ress telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: