3.  Pipe Connection Example

Connect the pipes between outdoor units, referencing the figure at 

right.

4.  Insulation Cover Installation

Install the insulation cover on the twinning kit after brazing the pipes and twinning kit. 

Insulate all refrigerant pipes. Insulate the high-pressure and low-pressure pipes separately, and pipes located inside the unit as well as 

the outside. Use heat-resistant insulation material (Heat resistant : at least 120°C [248°F], Thickness: high-pressure = 10 mm [3/8 in], 

low-pressure = 20 mm [13/16 in] ). Position the edges of the insulation cover and heat-resistant insulation material so as not to leave a 

gap, and then wrap the exterior perimeter of the pipe joints and middle with tape (field-supplied).

(1)  High-pressure side

(2)  Low-pressure side

Field piping

Field piping

Insulation material (field supply)

Insulation material 
(field supply)

Field piping

Twinning kit

Insulation cover

Tape (field supply)

Tape (field supply)

5.  Miscellaneous Notes

Secure the field-supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as 

necessary.

The pipe section before the twinning 

pipe must have at least 500 mm 

(19-11/16 in) of straight section.

Twinning kit

On-site piping

On-site piping

Tape (field-supplied)

To be gap free

Heat-resistant insulation material (field-supplied)

Heat-resistant insulation material (field-supplied)

Insulation cover

To be gap free

field-supplied pipe

field-supplied pipe

High-pressure 

twinning pipe

field-supplied pipe

Insulation cover Heat-resistant insulation material (field-supplied)

Tape (field-supplied)

Insulation covers can shrink. 

Overlap the tape as shown in the left 

figure so that there will be no gap in 

between the insulation cover or field-

installed insulation material.

Overlap margin of the tape

Insulation material  

(field supply)

Insulation material (field supply)

Tape (field supply)

Insulation cover

Tape (field supply)

Field piping

Field piping

Field piping

Twinning kit

Summary of Contents for CITY MULTI CMY-R100NCBK

Page 1: ...r wrong size connecting pipe is used air conditioning performance will suffer If leaked refrigerant comes in contact with a heat source such as a fan heater stove or electric grill toxic gases will be generated Improper installation may result in water leakage electric shock or fire Any presence of foreign substance or air can cause abnormal pressure rise or explosion If refrigerant leaks and come...

Page 2: ...0NCBK High pressure Low pressure OD22 2 7 8 ID28 58 1 1 8 2 OD28 58 1 1 8 ID34 93 1 3 8 CMY R300NCBK High pressure OD19 05 3 4 ID22 2 7 8 2 Low pressure OD34 93 1 3 8 ID41 28 1 5 8 3 List of field supplied parts Refrigerant pipes other than the ones provided in the kit Heat resistant insulation material for field supplied refrigerant pipes Insulation cover tape 2 Selecting the Correct Size Refrige...

Page 3: ...tion The section of the field supplied pipe that connects to the twinning pipe must have at least 500 mm 19 11 16 in of straight section If the straight section is less than 500 mm 19 11 16 in it may result in equipment damage 4 Pipe connection Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards A B If twinning pipe is installed above the base of the outdoor unit it...

Page 4: ...inning kit Insulation cover Tape field supply Tape field supply 5 Miscellaneous Notes Secure the field supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as necessary The pipe section before the twinning pipe must have at least 500 mm 19 11 16 in of straight section Twinning kit On site piping On site piping Tape field supplied To be gap ...

Reviews: