(A) Level signal 

  When the level signal is selected, the operation (only ON/OFF operation) for the central controller and 

the local remote controller are prohibited (except during normal operation). 

  When the emergency stop/normal operation signal is selected, the status will be changed from normal 

operation to emergency stop when the external input signal contact turns OFF to ON, and will be 
changed from emergency stop to normal operation when external input signal contact turns ON to OFF. 
Emergency stop signal will bring the air conditioners to stop, and canceling the emergency stop will not 
automatically restart these units. To go back to the previous operation status, they must be manually 
turned back on. 

  When ON/OFF input signal is selected, the status will be changed from OFF to ON when the external 

input signal contact turns OFF to ON. 

 
(B) Pulse signal 

Even if the ON signal is input during ON, the status will remain at the ON status. 

When the local remote controller is prohibited, the ON/OFF operation, operation mode selection and 

temperature setting from the local remote controller is prohibited. 

Set the pulse width (contact ON time) to 0.5 to 1.0 second. 

 
 

4-2 External output function 

(1) The function of external output 

The “ON” signal is output when one or more air conditioner are in the ON operation. 

The “Malfunction” signal is output when one or more air conditioner malfunctions. 

 

(2) Specification of external output interface 

CN2 

Lead wire 

Description of each terminal 

No. 1 

Green 

Common (0V) 

No. 2 

Black 

ON/OFF 

No. 3 

Brown 

Malfunction/Normal 

 

 

 

Summary of Contents for Central Controller GB-50A

Page 1: ...el GB 50A Instruction Book Contents Before using the controller please read this Instruction Book carefully to ensure correct operation Store this Instruction Book in a location that is easy to find 1 Safety 1 2 Introduction 3 3 Function 4 4 External input output function 8 ...

Page 2: ...curely install in a place which can withstand the weight of the controller If it is not enough the unit may fall and cause an injury Contact your dealer if the controller will not be used any more or will be scrapped Make sure that the controller is connected to a rated power supply If the controller is not connected to a rated power supply it may cause a fire or damage to the controller Do not re...

Page 3: ...cified temperature range Observe the specified temperature range when operating the controller If the controller is used outside the specified temperature range it may cause serious damage Be sure to check the operation temperature range in the operation manual Do not touch the switch with wet hands It may cause an electric shock Do not use the controller for special applications This product is d...

Page 4: ...B 50A IP address is 192 168 1 1 User Default user name Default password Managers administrator admin 2 Introduction Notes With the registration of GB 50A License Pack Web Monitor Annual Schedule Weekly Schedule Sending Error Mail and Maintenance Tool Advanced functions will be available Consult the dealer for information on other functions that require a license i e Charge Saving Energy Control As...

Page 5: ...independent OA processing unit or LOSSNAY in one group 1 16 units Note Indoor unit independent OA processing unit and LOSSNAY can not register to the same group Number of remote controllers in one group 1 2 Number of system controllers in one group 0 4 including the number of remote controller in one group 0 3 for groups which have one remote controller Number of indoor units interlocked with one ...

Page 6: ...nding on the model Start stop of interlocked equipment Lossnay Switching start Hi Lo stop collectively or for each group when connecting with interlocked equipment Lossnay However ventilation mode can not be selected for the interlocked equipment Prohibition of local control Selecting the items for which local control is prohibited collectively or for each group Items include start stop operation ...

Page 7: ...ng the 4 pin dip switch on SW2 Set this switch before turning the power on Note When setting IP addresses with the Initial Setting Web or the Initial Setting Tool set all four dipswitches on SW2 to OFF 1 2 3 4 Contents IP address OFF OFF OFF OFF Address that is set with Initial Setting Web or Initial Setting Tool Initial IP address setting is 192 168 1 1 OFF OFF OFF ON Starts from 192 168 1 1 OFF ...

Page 8: ...s for normal use ON OFF Setting is prohibited OFF ON Setting is prohibited ON ON Start up with the update mode The software can be updated with the normal mode If the update fails or the software does not work properly use this setting to update the software again SW1 3 and SW1 4 are always OFF Notes When 15 or fewer GB 50A units are used in the designated network for air conditioning it is recomm...

Page 9: ...l remote controller s operation will be prohibit 3 Perform ON OFF operation with level signal Only the ON OFF operation of the central controller and the local remote controller will be prohibit 4 Perform ON OFF operation prohibit permit operation with pulse signal Set the pulse width while the contact is ON to 0 5 to 1 0 second Settings for these functions can be set with the Initial Setting Web ...

Page 10: ... they must be manually turned back on When ON OFF input signal is selected the status will be changed from OFF to ON when the external input signal contact turns OFF to ON B Pulse signal Even if the ON signal is input during ON the status will remain at the ON status When the local remote controller is prohibited the ON OFF operation operation mode selection and temperature setting from the local ...

Page 11: ...10 ...

Page 12: ...11 ...

Reviews: