3 SPECIFICATIONS
3.2 Performance Specifications
19
3
3.2
Performance Specifications
Input module
NZ2GNSS2-8D DC input module
Item
NZ2GNSS2-8D
Station type
Remote station
Authentication Class
Authentication Class B
Network topology
Line topology, star topology, mixture of star topology and line topology, ring topology
Number of input points
Single wiring: 8 points, double wiring: 4 points
Rated input voltage
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
Rated input current
7.3mA TYP. (for 24VDC)
Maximum number of simultaneous input points
100%
ON voltage/ON current
12VDC or higher/3mA or higher
OFF voltage/OFF current
5VDC or lower/1.3mA or lower
Input resistance
2.6k
Input circuit response time
OFF
ON
0.4ms or less (24VDC)
ON
OFF
Safety remote station safety cycle time
2.0ms
Communication path response time
0.3ms
Safety remote station refresh response processing time
Safety remote station safety cycle time + Communication path response time
Safety remote station input response time
Input circuit response time + Input response time (1ms, 1.5ms, 5ms, 10ms, 20ms, 50ms, 70ms)
External power supply for
input part
Voltage
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
Current
100mA
Protection function
External power supply overvoltage protection function
Power supply current for input device (COM+)
0.4A/1 terminal
Input type
Negative common type
Withstand voltage
510VAC for 1 minute between all DC external terminals and ground
Insulation resistance
10M
or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity
Noise voltage 500Vp-p, noise width 1
s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree
IP2X
Wiring method for common
Input 8 points/common (spring clamp terminal block)
External interface
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (2-piece spring clamp terminal block (push-in))
I/O part, external power
supply part
40 points, 2-piece spring clamp terminal block (push-in)
Applicable wire size
Terminal block for module
power supply and FG
Stranded wire: 0.3 to 1.5
(22 to 16 AWG), terminal slot size: 2.8mm
2.0mm
I/O terminal block
Stranded wire: 0.5 to 1.5
(20 to 16 AWG)
Applicable solderless
terminal
Terminal block for module
power supply and FG
Page 44 Applicable solderless terminal
I/O terminal block
Page 49 Applicable solderless terminal
Multicast filter
Available
Cyclic transmission
RX/RY points
16 points
RWr/RWw points
4 points
SA\X / SA\Y points
SA\X: 16 points
Module power supply
Voltage
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
Current
160mA
Protection function
Module power supply overvoltage protection function, module power supply overcurrent protection
function
Fuse
1.6A (user-unchangeable)
Safety element
Type B, HFT = 1, SC 3
Summary of Contents for CC-Link IE-NZ2GNSS2-16DTE
Page 2: ......
Page 17: ...1 PRODUCT LINEUP 1 1 List of Products 15 1 MEMO ...
Page 35: ...4 PROCEDURES BEFORE OPERATION 33 4 MEMO ...
Page 162: ...160 APPX Appendix 7 Added and Changed Functions MEMO ...
Page 164: ...162 MEMO ...
Page 169: ......