136
APPX
Appendix 3 Remote Register
■
Communication speed (RWr0.b1)
The communication speed (RWr0.b1) indicates a communication speed at which the safety remote I/O module is operating.
• ON: 100Mbps
• OFF: 1Gbps
■
Error status flag (RWr0.b10)
The error status flag (RWr0.b10) turns on when an error occurs.
• Moderate errors and major errors
• Minor error
• When a moderate error or major error occurs, recovery from the error status is not possible unless the error
is cleared and the safety remote I/O module is restarted (by powering off and on the module or performing
remote reset).
• When a minor error occurs, five seconds after the cause of the error is eliminated, the error code (RWr1) is
automatically set to 0H and the error status flag (RWr0.b10) is turned off at the same time.
(1) Moderate error or major error occurred
Implemented with the safety remote I/O module
(1) Minor error occurred
(2) Minor error was eliminated
Implemented with the safety remote I/O module
0000H
ON
OFF
(1)
Error status flag
(RWr0.b10)
Error code
(RWr1)
Error code
OFF
ON
0000H
0000H
(1)
(2)
Error code
5 seconds
Error status flag
(RWr0.b10)
Error code
(RWr1)
Summary of Contents for CC-Link IE-NZ2GNSS2-16DTE
Page 2: ......
Page 17: ...1 PRODUCT LINEUP 1 1 List of Products 15 1 MEMO ...
Page 35: ...4 PROCEDURES BEFORE OPERATION 33 4 MEMO ...
Page 162: ...160 APPX Appendix 7 Added and Changed Functions MEMO ...
Page 164: ...162 MEMO ...
Page 169: ......