80
7 FUNCTIONS
7.5 Initial Operation Setting Function
7.5
Initial Operation Setting Function
This function sets whether the initial processing using the program is necessary or not when the data link is established. The
function enables the IO-Link module to operate (enabling the update of external I/O) with the program for initial processing not
being set.
Operation of the initial operation setting function
The operation of the initial operation setting function varies depending on the setting value of "Initial operation setting". When
setting parameters using Initial processing request flag (RWr0.b8) as an interlock as shown in the program example, set
"Initial operation setting" to "With initial processing".
For program examples of initial processing, refer to the following.
■
When "With initial processing" is set
When the data link is established, Initial processing request flag (RWr0.b8) turns on.
When Initial processing completion flag (RWw0.b8) is turned on, Initial processing request flag (RWr0.b8) turns off and
Remote READY (RWr0.b11) turns on.
The IO-Link module functions cannot be used until initial processing is completed.
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
RY0
Initial processing
request flag
(RWr0.b8)
Module power
supply
Processing of
the IO-Link module
External output
signal Y0
Initial processing
completion flag
(RWw0.b8)
Remote READY
(RWr0.b11)
Data link is
established.
Processing
executed at
the startup
The output
is turned on.
Controlled by the IO-Link module
Controlled by the program
Program
IO-Link module
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......