1 PART NAMES
15
1
LED names of the IO-Link module
This section describes the LEDs of the IO-Link module.
No.
Name
Description
(1)
DISPLAY1 LED
This LED turns on/off when the remote output signal turns on/off.
DISPLAY1 LED and DISPLAY2 LED work in the same way.
For example, use a relevant remote output signal in a program so that the sequence processing can be checked via the LED.
The LED also shows the result of a unit test.
■
Remote output signal
Green: Display LED1 and LED2 (RY20) are off, and Display LED1 and LED2 (RY21) are on.
Red: Display LED1 and LED2 (RY20) are on, and Display LED1 and LED2 (RY21) are off.
Orange: Display LED1 and LED2 (RY20) are on, and Display LED1 and LED2 (RY21) are on.
Red (flashing): A major error has occurred.
Off: Display LED1 and LED2 (RY20) are off, and Display LED1 and LED2 (RY21) are off.
■
Unit test
Green: The unit test result is normal.
Red: The unit test result is abnormal.
(2)
DISPLAY2 LED
(3)
US LED
Indicates the voltage status of the module/sensor power supply.
Green: The module/sensor power supply has no voltage error.
Red: The module/sensor power supply has a voltage error (18VDC or less).
Off: The module/sensor power supply is off or has a voltage error (11VDC or less).
UA LED
Indicates the voltage status of the actuator power supply.
Green: The actuator power supply has no voltage error.
Red (flashing): The actuator power supply has a voltage error (18VDC or less).
Red: The actuator power supply is off or has a voltage error (11VDC or less).
RUN LED
Indicates the operating status of the IO-Link module.
On: Operating normally.
Off: A module error has occurred.
ERR. LED
Indicates the error status of the IO-Link module.
On: A module error has occurred.
Off: Operating normally.
(1)
(2)
(3)
(6)
(4)
(5)
(7)
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......