13
CHAPTER 2 SPECIFICATIONS
2
2.
1 G
eneral
S
pecif
ic
at
ions
CHAPTER 2
SPECIFICATIONS
2.1
General Specifications
*1
Do not use or store the programmable controller under pressure higher than the atmospheric pressure at sea level.
Doing so may cause malfunction. When using the programmable controller under pressure, please consult your local
Mitsubishi representative.
*2
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises. Category II applies to equipment for which
electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is
2500V.
*3
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used. In pollution degree 2, only non-conductive pollution occurs. A temporary conductivity caused by an
accidental condensation may also occur occasionally.
Item
Specifications
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-25 to 75
Operating ambient
humidity
10 to 90%RH, non-condensing
Storage ambient
humidity
Vibration resistance
Compliant with
JIS B 3502 and
IEC 61131-2
Frequency
Constant
acceleration
Half amplitude
No. of sweeps
Under
intermittent
vibration
5 to 8.4Hz
3.5mm
10 times each in
X, Y, and Z
directions
8.4 to 150Hz
9.8m/s
2
Under
continuous
vibration
5 to 8.4Hz
1.75mm
8.4 to 150Hz
4.9m/s
2
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
2
, 3 times each in X, Y, and Z directions)
Operating
atmosphere
No corrosive gas
Operating altitude
0 to 2000m
Installation location
Inside the control panel
Overvoltage
category
II or less
Pollution degree
2 or less
Summary of Contents for CC-Link-AnyWire Bitty Bridge
Page 1: ...CC Link AnyWire Bitty Bridge Module User s Manual NZ2AW1C1BY ...
Page 2: ......
Page 9: ...7 Memo ...
Page 14: ...12 Memo ...
Page 24: ...22 2 4 External Dimensions Unit mm 15 4 3 85 141 5 DIN rail 3 8 2 5 66 69 40 100 51 ...
Page 53: ...51 CHAPTER 10 CC LINK I O RESPONSE TIME 10 Memo ...
Page 73: ......