2 SPECIFICATIONS
2.1 General Specifications
15
2
2
SPECIFICATIONS
2.1
General Specifications
The following table lists the general specifications.
*1 Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction.
When using the programmable controller under pressure, please consult your local Mitsubishi representative.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category
applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for the equipment with the rated voltage of 300V or less is 2500V.
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
In pollution degree 2, only non-conductive pollution occurs. A temporary conductivity caused by an accidental condensation may also
occur occasionally.
*4 The equipment can also be used outside the control panel, provided that environmental conditions such as operating ambient
temperature and operating ambient humidity are met.
Item
Specifications
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-25 to 75
Operating ambient
humidity
5 to 95%RH, non-condensing
Storage ambient
humidity
Vibration resistance
Compliant with IEC
61131-2 and JIS B
3502
Frequency
Constant
acceleration
Half amplitude
Number of sweeps
Under intermittent
vibration
5 to 8.4Hz
3.5mm
10 times each in X,
Y, and Z directions
8.4 to 150Hz
9.8m/
Under continuous
vibration
5 to 8.4Hz
1.75mm
8.4 to 150Hz
4.9m/
Shock resistance
Compliant with IEC 61131-2 and JIS B 3502 (147m/
, 3 times each in X, Y, and Z directions)
Operating
atmosphere
No corrosive gas
Operating altitude
0 to 2000m
Installation location
Inside a control panel
Overvoltage
category
or less
Pollution degree
2 or less
Equipment class
Class
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......