Mitsubishi Electric AJ65DBTB1-32T1 User Manual Download Page 4

 

2. 各部の名称と設定 

2. Part Names and Settings

 

 

80

4

70 (2.76)

80

4

17

(6

.69)

16

(6

.34)

64 (2.52)

55 (2.17)

2-φ5取付穴(M4取付ネジ)

Mounting hole 

(M4 mounting screw)

Unit: mm (inch)

(0.16)

(3.15)

CTLG

CTL+

NC

24G

NC

NC

DB

DG

DA

SLD

+24V

NC

(FG)

24G

Y12

Y14

Y16

Y19

Y1B

Y1D

Y1F

Y8

YA

YC

YE

Y1

Y3

Y5

Y7

Y0

Y2

Y4

Y6

Y9

YB

YD

YF

-32T1

Y1E

Y1C

Y1A

Y18

Y17

Y15

Y13

COM4

COM3

COM1

COM2

Y10

Y11

AJ65DBTB1

STATION NO.

1

0

3 2

6

5

4

8

7

9

1

0

3 2

6

5

4

1

0

3 2

4

B RATE

17

PW

4

5

6

7

0

1

2

3

8

9

A

B

C

D

E

F

12

11

10

13

16

15

14

L ERR.

L RUN

18

19

1A

1B

1C

1D

1E

1F

×

10

×

A

J65DBTB1-32T1

 

  

No.  名    称 

内    容 

LED 名 

確認内容 

PW 

点灯: 電源 ON。 
消灯: 電源 OFF。 

L RUN 

点灯: 交信正常時。 
消灯: 交信断時(タイムオ-バエラー)。 
 

L ERR. 

点灯: 交信エラー時。 
一定間隔で点滅: 

通電中に局番設定/伝送速度設定スイッ
チの設定を変更したとき。 

不定間隔で点滅: 

終端抵抗の設定が違っている,ユニット,
CC-Link 専用ケーブルがノイズの影響を
受けているとき。 

消灯: 交信正常時。 
 
 
 

① 

動作表示 
LED 

Y0~1F 

点灯: 出力 ON,消灯:出力 OFF。 
 

設定値 

伝送速度 

156 kbps 

625 kbps 

2.5 Mbps 

5.0 Mbps 

 

10 Mbps 

 

② 

伝送速度 
設定 

伝送速度は必ず上記の範囲で設定してください。 

③ 

局番設定 
スイッチ 

リモート I/O ユニットの局番は,必ず 01~64 の範囲で設
定してください。(*1) 
・“×10”は,局番の 10 の位を設定します。 
・“×1”は,局番の 1 の位を設定します。 

④  端子台 

出力ユニット電源,伝送,出力信号の接続用端子台です。
 

*1:局番は重複して設定できません。 

 

 

No.

Item Description 

LED name

Confirmation details 

PW 

ON:  Power supply ON. 
OFF:  Power supply OFF. 

L RUN 

ON: Normal 

communication.  

OFF:  Communication shut off 

(time expiration error). 

L ERR. 

ON:  Communication data error. 
Flash at regular intervals: 

Indicates that the station number 
setting or transmission speed setting 
switch position was changed while 
power is ON. 

Flash at irregular intervals:   

When the setting of the terminal 
resistor is wrong; when the cable for 
the module or CC-Link is affected by 
noise. 

OFF: Normal communication. 

Operating 
status 
indicator 
LEDs 

Y0 to 1F 

ON: Output 

ON. 

OFF: Output OFF. 

Setting value 

Transmission speed 

0 156 

kbps 

1 625 

kbps 

2 2.5 

Mbps 

3 5.0 

Mbps 

 

4 10 

Mbps 

Trans- 
mission 
speed 
setting 

Be sure to set the transmission speed within the above 
range. 

Station 
number 
setting 
switches 

Be sure to set the station numbers of remote I/O module 
within the range of 01 to 64. (*1) 
• “ 10”sets the tens place of the station number. 
• “ 1”sets the units place of the station number. 

Terminal 
block 

A terminal block for connection to the power supply, 
transmission and output signals. 

*1: Duplicate station number cannot be set. 

 

Summary of Contents for AJ65DBTB1-32T1

Page 1: ...e communication error station will be in the following condition Configure an interlocking circuit in a sequence program using the communication status information so that the safety of the overall system is always maintained Accident may occur due to output error or malfunction Output points from remote I O station will be all switched off Output could be switched on or off when a problem occurs ...

Page 2: ...he product Mounting removing the terminal block is limited to 50 times after using a product IEC61131 2 compliant Always make sure to touch the grounded metal to discharge the electricity charged in the body etc before touching the module Failure to do so may cause a failure or malfunctions of the module DISPOSAL PRECAUTIONS CAUTION When disposing of this product treat it as industrial waste 1 Spe...

Page 3: ...Y8 TB42 Y18 TB18 Y9 TB43 Y19 TB19 YA TB44 Y1A TB20 YB TB45 Y1B TB21 YC TB46 Y1C TB22 YD TB47 Y1D TB23 YE TB48 Y1E TB24 YF TB49 Y1F TB25 COM2 TB50 COM4 絶縁 DC DC Y0 Y1 Y2 Y3 Y4 Y5 Y6 9 8 10 11 12 13 14 Y7 Y8 Y9 YA YB 16 15 17 18 19 YC 20 YD YE YF 22 21 23 24 25 COM2 DA DB DG SLD Empty 24G 2 3 4 5 6 7 1 Empty COM1 Y10 Y11 Y12 Y13 Y14 Y15 Y16 34 33 35 36 37 38 39 Y17 Y18 Y19 Y1A Y1B 41 40 42 43 44 Y1C...

Page 4: ... 出力ユニット電源 伝送 出力信号の接続用端子台です 1 局番は重複して設定できません No Item Description LED name Confirmation details PW ON Power supply ON OFF Power supply OFF L RUN ON Normal communication OFF Communication shut off time expiration error L ERR ON Communication data error Flash at regular intervals Indicates that the station number setting or transmission speed setting switch position was changed while power is ON Flash...

Reviews: