Air Handling Unit Interface
AHU-KIT-SP
MORIKAWA
SPECIFICATION
PSZ000Z308
12/38
MODEL NAME
MODEL TYPE
ISSUE
CLASSIFICATION
DWG NO.
REV.MARK PAGE
21.09.17
Cooling
Heating
Thi-R1
U-bend
Evaporating temperature
Condensing temperature
Anti-freezing protection
Thi-R2
Capillary
Evaporating temperature
Outlet temperature
Anti-freezing protection
Thi-R3
Header
Outlet temperature
Inlet gas temperature
EEV-control
Detected temperature
Mounting
position
Purpose
Input circuit
●Mounting guidelines for sensors
Mounting position of the sensor (example)
Installing temperature sensors
Correctly securing temperature sensors (Example)
When installing the temperature sensors, make sure that they have optimum contact
with the surface to be measured.
Secure with a wide
-
band hose clamp.
[Important]
Using cable ties will lead to faulty and squashed temperature sensors.
Use wide
-
band hose clamps for fastening.
Installation locations of the heat exchanger sensor
Mounting position of temperature sensors (example)
No. Designation
1
Temperature sensor cable
2
Temperature sensor
3
Fastener
Function of each heat exchanger sensor