6-2. Items not included
The following items are required to install the AE-200/AE-50.
Items not included
Specifications
Electrical box
(required only for installation
method 2)
Model: PAC-YG84UTB-J
Metal control box
(required only for installation
methods 3 and 4)
Must be suitable for the AE-200/AE-50 installation.
Minimum metal thickness when using installation method 4: 200 mm (7-7/8 in)
Locknuts and bushing
Must be suitable for the conduit tube to be used.
Sleeved ring terminal
M3.5 ring terminal (for AC power cables (L/L1, N/L2) and M-NET transmission cables (A, B,
S))
M4 ring terminal (for protective ground wire)
AC power cable/Protective
ground wire
Type: Sheathed vinyl wire (should not be lighter than ordinary PVC sheathed flexible cord
IEC 60227.)
(designation 60227 IEC 52)
*1
Size: 0.75 to 2.00 mm² (ø1.0 to ø1.6 mm), AWG 18 to 14
Protective ground wire color: green/yellow
* Use a wire with an appropriate diameter so that the wire can be fixed with the cable tie below the
terminal block. A diameter of 10 mm (25/64 in) is recommended.
Transmission cable
Type: Sheathed vinyl cable
● CPEVS ø1.2 to ø1.6 mm
● CVVS Min. 1.25 to 2 mm²
* CPEVS: PE
*2
insulated PVC
*2
jacketed shielded communication cable
* CVVS: PVC
*2
insulated PVC
*2
jacketed shielded control cable
LAN cable
Category 5 or above straight cable (Max. 100 m (328 ft))
Switching HUB
A communication speed of 100 Mbps or faster is recommended.
Overcurrent
breaker (fuse or
circuit breaker)
Fuse
Rated current: 3 A
* When using a fuse, use it in combination with a switch (rated current: 3 A).
Circuit breaker
Type: Bipolar (2P2E)
Contact distance: Min. 3 mm (1/8 in)
Rated current: 3 A
Earth leakage breaker
Type: Bipolar (2P2E)
Contact distance: Min. 3 mm (1/8 in)
Rated current: 3 A
Rated current sensitivity: 30 mA
Operation time: Max. 0.1 sec
*1 For the U.S. and Canada: designation NEC (NEPA70) or CEC
*2 PE: Polyethylene, PVC: Polyvinyl chloride
6-3. Items sold separately
Items sold separately
Model name
Remarks
Electrical box
PAC-YG84UTB-J
Required only for installation method 2
Mounting kit
L-fittings
PAC-YG86TK-J
Required only for installation method 4
DIN rail attachments
External input/output adapter
PAC-YG10HA-E
Required when using the external input/output function