(N) Operation via communication and its settings
54
When Pr.544 = "1" (compatible with CC-Link Ver.1)
• Remote I/O (32 points)
Same as when
Pr.544
= 0 (Refer to
• Remote register
For the FR-A800-E, when
Pr.804
="3 or 5" during torque control under Real sensorless vector control or vector control, a torque command value
is set in RWwn+1.
"n" indicates a value determined according to the station number setting.
When Pr.544 = "12" (Compatible with the double setting of CC-Link Ver.2)
• Remote I/O (32 points)
Same as when
Pr.544
= 0 (Refer to
• Remote register
For the FR-A800-E, when
Pr.804
="3 or 5" during torque control under Real sensorless vector control or vector control, a torque command value
is set in RWwn+1.
"n" indicates a value determined according to the station number setting.
When Pr.544 = "14 or 24" (compatible with the quadruple setting of CC-Link Ver.2)
• Remote I/O (32 points (64 points occupied))
Same as when
Pr.544
= 0 (Refer to
• Remote register
Address
Description
Refer to
page
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
Upper 8 bits
Lower 8 bits
RWwn
Monitor code 2
Monitor code 1
RWrn
First monitor value
RWwn+1
Set frequency (0.01 Hz increments) /
torque command
RWrn+1
Second monitor value
RWwn+2
Link parameter
extended setting
Instruction code
RWrn+2
Reply code 2
Reply code 1
RWwn+3
Write data
RWrn+3
Read data
Address
Description
Refer to
page
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
Upper 8 bits
Lower 8 bits
RWwn
Monitor code 2
Monitor code 1
RWrn
First monitor value
RWwn+1
Set frequency (0.01 Hz increments) /
torque command
RWrn+1
Second monitor value
RWwn+2
Link parameter
extended setting
Instruction code
RWrn+2
Reply code 2
Reply code 1
RWwn+3
Write data
RWrn+3
Read data
RWwn+4
Monitor code 3
RWrn+4
Third monitor value
RWwn+5
Monitor code 4
RWrn+5
Fourth monitor value
RWwn+6
Monitor code 5
RWrn+6
Fifth monitor value
RWwn+7
Monitor code 6
RWrn+7
Sixth monitor value
Address
Description
Refer to
page
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
Upper 8 bits
Lower 8 bits
RWwn
Monitor code 2
Monitor code 1
RWrn
First monitor value
RWwn+1
Set frequency (0.01 Hz increments)
RWrn+1
Second monitor value
RWwn+2
Link parameter
extended setting
Instruction code
RWrn+2
Reply code 2
Reply code 1
RWwn+3
Write data
RWrn+3
Read data
RWwn+4
Monitor code 3
RWrn+4
Third monitor value
RWwn+5
Monitor code 4
RWrn+5
Fourth monitor value
RWwn+6
Monitor code 5
RWrn+6
Fifth monitor value
RWwn+7
Monitor code 6
RWrn+7
Sixth monitor value
RWwn+8
Faults history No.
H00
RWrn+8
Faults history No.
Fault data
RWwn+9
PID set point (0.01% increments)
RWrn+9
Fault record (output frequency)
RWwn+A
PID measured value (0.01% increments)
RWrn+A
Fault record (output current)
RWwn+B
PID deviation (0.01% increments)
RWrn+B
Fault record (output voltage)
RWwn+C
Torque command or torque limit
/
Torque command or torque limit (1st
quadrant)
RWrn+C
Fault record (energization time)