(N) Operation via communication and its settings
38
• Remote RUN
The external device executes the remote RUN to the inverter.
• Request data
• Response data
None
• Remote STOP
The external device executes the remote STOP to the inverter.
• Request data
• Response data
None
• CPU (inverter) model name read
The external device reads the model name and model code of the inverter.
• Request data
• Response data
Error code
When the end code is other than "0" (failed completion), one of the error codes shown in the following table will be stored.
Item
Description
Mode
Forced execution of the remote RUN is not allowed.
H0100
Forced execution of the remote RUN is allowed.
H0300
Clear mode
Devices are not cleared (initialized).
H00
Devices are cleared.
H01, H02
Item
Description
Model
The inverter model is stored. Up to 16 characters can be stored. If the model name is shorter than 16
characters, a space (H20) is stored instead of a character.
(Example) FR-A800-E inverter: FR-A800-E
Model code
Fixed to H054E
Error code
Fault definition
H4031
The device outside of the range is specified.
H4080
Request data fault
H4A01
The network with the No. set in the routing parameter does not exist.
(The destination network No., destination station No., or destination unit I/O No. is different from that of the target
inverter.)
HC059
The command or subcommand is specified incorrectly. Or, an unspecified command is received.
HC05B
The inverter cannot read/write data from/to the specified device.
HC05C
The request message has an error.
HC060
The requested operation has an error.
Example) Data is specified incorrectly for the bit device.
HC061
The request data length is inconsistent with the number of data.
HCEE1
The request message size exceeds the allowable range.
HCEE2
The response message size exceeds the allowable range.
H01 H10 H00 H00
H00
Mode
Clear
mode
H02 H10 H00 H00 H01 H00
H01 H01 H00 H00
Model
Model
code