(N) Operation via communication and its settings
20
The setting is applied after an inverter reset or power-ON.
NOTE
• The monitored items and parameter settings can be read during communication with the
Pr.1432 Ethernet communication
check time interval
= "0" setting, but an inverter fault occurs instantly when the operation mode is switched to the NET
operation mode. When the NET operation mode is selected as the start-up operation mode, communication is performed
once, then an Ethernet communication fault (E.EHR) occurs.
To perform operation or parameter writing via communication, set
Pr.1432
to "9999" or a value larger than the communication
cycle or retry time setting. (Refer to
1432
N644
Ethernet communication
check time interval
9999
0
Ethernet communication is available, but the inverter trips in the
NET operation mode.
0.1 to 999.8 s
Set the interval of the communication check (signal loss
detection) time for all devices with IP addresses in the range
specified for Ethernet command source selection (
Pr.1449 to
Pr.1454
).
If a no-communication state persists for the permissible time or
longer, the inverter will trip.
9999
No communication check (signal loss detection)
1424
N650
Ethernet communication
network number
1
1 to 239
Enter the network number.
1425
N651
Ethernet communication
station number
1
1 to 120
Enter the station number.
1442
N660
Ethernet IP filter address
1
0
0 to 255
Set the range of connectable IP addresses for the network
devices.
(When
Pr.1442 to Pr.1445
= "0 (initial value)", the function is
invalid.)
1443
N661
Ethernet IP filter address
2
0
0 to 255
1444
N662
Ethernet IP filter address
3
0
0 to 255
1445
N663
Ethernet IP filter address
4
0
0 to 255
1446
N664
Ethernet IP filter address
2 range specification
9999
0 to 255, 9999
1447
N665
Ethernet IP filter address
3 range specification
9999
0 to 255, 9999
1448
N666
Ethernet IP filter address
4 range specification
9999
0 to 255, 9999
1449
N670
Ethernet command
source selection IP
address 1
0
0 to 255
To limit the network devices that send the operation or speed
command through the Ethernet network (Modbus/TCP or CC-
Link IE Field Network Basic), set the range of IP addresses of
the devices.
When
Pr.1449 to Pr.1452
= "0 (initial value)", no IP address is
specified for sending commands through the Ethernet network.
In this case, operation through the Ethernet network (Modbus/
TCP or CC-Link IE Field Network Basic) is not available.
When four or more clients attempt a connection to the inverter
during Modbus/TCP communication, the connection attempted
from outside of the IP address range set for Ethernet command
source selection may be forced to be closed.
1450
N671
Ethernet command
source selection IP
address 2
0
0 to 255
1451
N672
Ethernet command
source selection IP
address 3
0
0 to 255
1452
N673
Ethernet command
source selection IP
address 4
0
0 to 255
1453
N674
Ethernet command
source selection IP
address 3 range
specification
9999
0 to 255, 9999
1454
N675
Ethernet command
source selection IP
address 4 range
specification
9999
0 to 255, 9999
Pr.
Name
Initial
value
Setting
range
Description