(M) Monitor display and monitor output signal
13
2
GROUP
M
2.4
(M) Monitor display and monitor output
signal
2.4.1
Output terminal function selection
The initial value is for standard models and IP55 compatible models.
The initial value is for separated converter types.
For the other settings, refer to the Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter.
The other available settings depend on the inverter. For details, refer to the description of
Pr.190 to Pr.196 (Output terminal function
selection)
in the Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter.
The parameter is used when the CC-Link IE Field Network Basic is selected. (Refer to
Inverter-to-inverter linkup (LNK) signal
• The Inverter-to-inverter linkup (LNK) signal is available to check that the master-slave communication is established. (For
the details of the inverter-to-inverter link function, refer to
• To use the LNK signal, set "242 (positive logic) or 342 (negative logic)" in any of
Pr.190 to Pr.196 (Output terminal
function selection)
to assign the function to the output terminal.
NOTE
• Changing the terminal assignment using
Pr.190 to Pr.196 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Purpose
Parameter to set
Refer to
page
To assign functions to the output
terminals
Output terminal function
assignment
P.M400 to P.M406,
P.M410 to P.M412
Pr.190 to Pr.196,
Pr.313 to Pr.315
Use the following parameters to change the functions of the open collector output terminals, relay output terminals, or
virtual terminals of CC-Link IE Field Network Basic.
Pr.
Name
Initial
value
Initial set signal
Setting range
190
M400
RUN terminal
function selection
Open
collector
output
terminal
0
RUN (Inverter running)
Inverter-to-inverter linkup (LNK) signal:
242 (positive logic), 342 (negative
logic)
191
M401
SU terminal
function selection
1
SU (Up to frequency)
192
M402
IPF terminal
function selection
IPF (Instantaneous power
failure/undervoltage)
9999
No function
193
M403
OL terminal
function selection
3
OL (Overload warning)
194
M404
FU terminal
function selection
4
FU (Output frequency
detection)
195
M405
ABC1 terminal
function selection
Relay
output
terminal
99
ALM (Fault)
196
M406
ABC2 terminal
function selection
9999
No function
313
M410
DO0 output selection
9999
No function
Inverter-to-inverter linkup (LNK) signal:
242 (positive logic), 342 (negative
logic)
314
M411
DO1 output selection
9999
No function
315
M412
DO2 output selection
9999
No function
Master/slave
Signal ON condition
Signal OFF condition
Master
The inverter receives a response from all the slave
inverters during initial communication.
• The inverter does not receive a response from a slave
in communication.
• The inverter detects a signal loss.
Slave
The inverter returns a response to the master.
• The inverter does not receive any request from the
master.
• The inverter detects a signal loss.