User’s Manual

(Hardware)

AJ61BT11

A1SJ61BT11

Thank you for buying the general-purpose programmable controller 
MELSEC-A Series.

© 2000 MITSUBISHI ELECTRIC CORPORATION

CC-Link

System Master/Local Module

Prior to use, please read both this manual and detailed manual 
thoroughly and familiarize yourself with the product.

MODEL

AJ61BT11-U-H-JE

MODEL

CODE

13JT18

IB(NA)-0800146-F(1612)MEE

Summary of Contents for A1SJ61BT11

Page 1: ...grammable controller MELSEC A Series 2000 MITSUBISHI ELECTRIC CORPORATION CC Link System Master Local Module Prior to use please read both this manual and detailed manual thoroughly and familiarize yourself with the product MODEL AJ61BT11 U H JE MODEL CODE 13JT18 IB NA 0800146 F 1612 MEE ...

Page 2: ...manual in a safe place for future reference DESIGN PRECAUTIONS WARNING For the operating status of each station after a data link failure refer to Chapter 5 in the user s manual The master station or local station cannot detect errors when a station specified as an error invalidated station becomes communication error CAUTION Do not install the control lines or communication cables together with m...

Page 3: ...h the specified torque Incorrect mounting may cause malfunction failure or drop of the module Shut off the external power supply for the system in all phases before mounting or removing the module Failure to do so may result in damage to the product Do not directly touch any conductive part of the module Doing so can cause malfunction or failure of the module WARNING Shut off the external power su...

Page 4: ...ll the control lines and communication cables together with the main circuit lines or power cables Doing so may cause malfunction due to noise Use applicable solderless terminals and tighten them within the specified torque range If any spade solderless terminal is used it may be disconnected when the terminal screw comes loose resulting in failure When disconnecting the cable from the module do n...

Page 5: ...assemble or modify the modules Doing so may cause failure malfunction injury or a fire Shut off the external power supply for the system in all phases before mounting or removing the module Failure to do so may cause the module to fail or malfunction After the first use of the product do not mount remove the module to from the base unit and the terminal block to from the module more than 50 times ...

Page 6: ...ENDED OR EXCLUDED BY INSTRUCTIONS PRECAUTIONS OR WARNING CONTAINED IN MITSUBISHI S USER INSTRUCTION AND OR SAFETY MANUALS TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT Prohibited Application Prohibited Applications include but not limited to the use of the PRODUCT in Nuclear Power Plants and any other power plants operated by Power companies and or any other cases in which the public could be...

Page 7: ...ns provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail safe redundant or other safety features which exceed the general specifications of the PRODUCTs are required For details please contact the Mitsubishi representative in your region ...

Page 8: ...nce with the EMC and Low Voltage Directives Section 1 1 2 1 to 2 2 Chapter 3 4 1 5 1 6 1 Dec 2011 IB NA 0800146 E COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES Section 5 1 SAFETY PRECAUTIONS Chinese CONDITIONS OF USE FOR THE PRODUCT Dec 2016 IB NA 0800146 F Chapter 3 Section 6 2 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent license...

Page 9: ...2 1 1 Maximum overall cable distance 4 2 2 CC Link dedicated cable 4 3 Name and Setting of Each Component 5 4 Loading and Installation 10 4 1 Handling precautions 10 4 2 Installation environment 11 5 External Wiring 12 5 1 Wiring the CC Link dedicated cable 12 6 External Dimensions 14 6 1 AJ61BT11 14 6 2 A1SJ61BT11 15 ...

Page 10: ...ertain measures may be necessary Please refer to one of the following manuals User s manual for the CPU module used User s manual hardware for the CPU module or base unit used The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives 2 Additional measures To ensure that this product maintains EMC and Low Voltage Directives please refer to one o...

Page 11: ... cable length between station and station uniformly to 20cm or more are indicated below 1 All modules configuring the CC Link system must use Version 1 10 2 All data link cables must be Version 1 10 compatible CC Link dedicated cable 1 Checking Version 1 10 The CC Link logo is printed on the front of the module or on the rating plate for the Version 1 10 modules Item name Number of items AJ61BT11 ...

Page 12: ... I O stations 64 B Number of remote device stations 42 C Number of local stations standby master stations intelligent device stations 26 Number of occupied stations when local station 1 to 4 stations 1 switched using the DIP switch Maximum link points for one system Remote I O RX RY Remote register RWw Remote register RWr 2048 points 256 points master station remote local station 256 points remote...

Page 13: ... with other cable types If different cable types are used together normal data transmission is not guaranteed Also attach the terminating resistor which matches the cable Refer to section 5 1 RAS function Auto return function Slave station cutoff function Error detection by the link special relay register Number of parameter registration to E2 PROM 10000 times Number of occupied I O points 32 poin...

Page 14: ...s Manual 2 2 CC Link dedicated cable Use the CC Link dedicated cables in a CC Link system If a cable other than the CC Link dedicated cable is used the performance of the CC Link system cannot be guaranteed For the specifications of the CC Link dedicated cables or any other inquiries visit the following site CC Link Partner Association website www cc link org Remarks For details refer to the CC Li...

Page 15: ...5 3 Name and Setting of Each Component This section explains the name and setting of each component of AJ61BT11 and A1SJ61BT11 6 5 4 3 2 1 2 6 5 4 3 1 ...

Page 16: ...overlapping With the exception of the first station number overlapping PRM ON Parameter setting error TIME ON Cable disconnection or no response from all stations due to noise in a communication path LINE ON Cable disconnection or transmission path is affected by noise etc L RUN ON In data link host 1 L ERR ON Communication error host Flashing at regular intervals The setting s of switches 2 to 5 ...

Page 17: ...T11 A1SJ61BT11 Set the module operation status setting at shipment 0 Number Name 0 Online remote net mode 1 Online remote I O net mode 2 Offline 3 Line test 1 3 4 Line test 2 3 5 Parameter confirmation test 3 6 Hardware test 7 Setting error the SW LED on 8 to A Setting prohibited B to F Setting error the SW LED on 4 Transmission speed setting switch AJ61BT11 A1SJ61BT11 Set the module transmission ...

Page 18: ...ons SW5 SW6 1 station OFF OFF 2 stations 4 OFF ON 3 stations 4 ON ON 4 stations ON OFF SW7 Unusable Always off SW8 Module mode OFF ON Intelligent mode I O mode 6 Terminal block Connect the CC Link dedicated cable for data link Refer to Section 5 1 for how to connect the cables Note that the following terminals are connected inside the module SLD terminal No 8 and FG terminal No 10 NC terminal No 7...

Page 19: ...e setting is changed while the module power supply is on reset the programmable controller CPU or turn off and then on the module power supply again Important Do not use station number 64 in a system where the waiting master station exists When it is used the station number 64 will not communicate correctly ...

Page 20: ...tion 4 Solderless terminals with insulation sleeve cannot be used for the terminal block It is recommended that the wiring connecting sections of the solderless terminals will be covered with a marking tube or an insulation tube 5 Before handling the module touch a grounded metal object to discharge the static electricity from the human body Failure to do so may cause the module to fail or malfunc...

Page 21: ...the terminal block If the terminal block is mounted or removed without turning off the power supply to the applicable station correct data transmission cannot be guaranteed 2 Power off the system in advance when removing the terminating resistor to change the system If the terminating resistor is removed and mounted while the system is energized normal data transmission will not be guaranteed ...

Page 22: ...nect the terminating resistors supplied with each module at both ends of the CC Link system Connect the terminating resistors across DA and DB When a T branch system is configured some restrictions are applied to the use of the A 1S J61BT11 A 1S J61QBT11 as the master station Refer to the CC Link System Master Local Module User s Manual for details 5 The terminating resistors to be connected vary ...

Page 23: ...ote module CC Link dedicated cable CC Link dedicated cable Terminating resistor DG DG SLD FG DB DA SLD FG DB DA FG SLD DG DB DA Terminating resistor Master module Local module Blue Yellow White Yellow White Blue Yellow White Blue Yellow White Blue ...

Page 24: ...14 6 External Dimensions 6 1 AJ61BT11 Unit mm inch 37 5 1 48 23 1 0 90 2 0 08 250 9 84 129 1 5 08 106 4 17 4 2 0 17 4 2 0 17 ...

Page 25: ...15 6 2 A1SJ61BT11 Unit mm inch 24 0 94 6 5 0 26 93 6 3 69 34 5 1 36 130 5 12 ...

Page 26: ...No 12 Jakarta Pusat 10340 Indonesia Tel 62 21 3192 6461 MITSUBISHI ELECTRIC INDIA PVT LTD Pune Branch Emerald House EL 3 J Block M I D C Bhosari Pune 411026 Maharashtra India Tel 91 20 2710 2000 USA MITSUBISHI ELECTRIC AUTOMATION INC 500 Corporate Woods Parkway Vernon Hills IL 60061 U S A Tel 1 847 478 2100 Turkey Sales office Tel Country Region Sales office Tel Country Region Mexico MITSUBISHI EL...