background image

 1. General Description 

This user's manual describes the specification, name of each part,
wiring, etc. of the A1S64TCTT-S1 Temperature Control Module
(Hereafter abbreviated as A1S64TCTT-S1) A1S64TCTTBW-S1
Temperature Control Module with Disconnection Detection Function
(Hereafter abbreviated as A1S64TCTTBW-S1).
A1S64TCTT-S1 and A1S64TCTTBW-S1 abbreviated as A1S64TC.
After unpacking, confirm that there is the following products.

Item

A1S64TCTT-S1

Main body

A1S64TCTTBW-S1

Main body

A1S64TCTT-S1

1

-

A1S64TCTTBW-S1

-

1

 2. Performance Specification 

The A1S64TC performance specification is indicated in Table 2.1.

Table 2.1 A1S64TC performance specification

Specification

Item

A1S64TCTT-S1

A1S64TCTTBW-S1

Control output value

Transistor output

Temperature input points

4-channel/module

Supported thermocouple

Refer to Table 2.2

Ambient
temperature:
23

5

Full scale

(

0.3%) 

1 digit*2

Specification
accuracy

Ambient
temperature:
0 to 55

Full scale

(

0.7%) 

1 digit*2

Temperature
measurement

value: -100
or higher

Within 

1.0

Temperature
measurement
value: -150 to
-100

Within 

2.0

Accuracy
*1

Cold-junction
compensation
temperature
accuracy
(ambient
temperature:
0 to 55

)

Temperature
measurement
value: -200 to
-150

Within 

3.0

Sampling cycle

0.5s/4-channel

Control output cycle

1 to 100

Effects of the external resistance

0.35

V/

Input impedance

1M

 or more

Input filter

1 to 100S (0: input filter off)

Sensor compensation value setting

Software version A

  -5.00 to   5.00%

Software version B or later -50.00 to 50.00%

Operation when there is an input
disconnection

Upscale processing

Temperature control method

PID ON/OFF pulse or 2-position control

PID constant setting

Auto-tuning setting is possible

Proportional region (P)

0.0 to 1000.0% (0.0: 2-position control)

Integral time (I)

1 to 3600s

PID
constant
range

Derivative time (D)

1 to 3600s (Set 0 for PI control)

Set value range

Within the temperature range set with the
thermocouple to be used.

Blind sector setting range

0.1 to 10.0%

Output signal

ON/OFF Pulse

Rated load voltage

10.2 to 30VDC

Maximum load current

0.1A/point
0.4A/common

Maximum inrush current

0.4A 10ms

Maximum voltage drop
when ON

0.1VDC (TYP) 0.1A
2.5VDC (MAX) 0.1A

Transistor
output

Response time

OFF

ON: Less than 2ms

ON

OFF: Less than 2ms (resistor load)

Insulation method

Between the thermocouple input and
grounding: Transformer insulation
Between the thermocouple input and
channel: Transformer insulation

Current sensor

-

URD manufactured
current sensor*3
CTL-12-S36-8
(0.0 to 100.0A)
CTL-6-P-H
(0.00 to 20.00A)
(Former model, CTL-
6-P is also
applicable.)

Input method

Multiplexor method A/D conversion

Heater
disconnection
specification

Alert delay count

3 to 255

Table 2.1 A1S64TC performance specification (continued)

Specification

Item

A1S64TCTT-S1

A1S64TCTTBW-S1

I/O occupied points

32 points

Connection terminal

20 points terminal block

Supported cable size

0.75 to 1.5mm

Supported solderless terminal

R1.25-3,1.25-YS3,RAV1.25-3,V1.25-YS3A

Internal consumed current (mA)

330

420

Weight (kg) [lb]

0.27[0.59]

0.3[0.66]

External dimensions (mm) [inch] 130[5.12](H)

34.5[1.36](w)

93.6[3.69](D)

For the noise resistance, dielectric withstand voltage, and insulation
resistance for the PC system which uses this module, refer to the power
module specification found in the CPU Module User's Manual.

*1: Calculate the accuracy as follows:

(Accuracy) = (specification accuracy) + (cold-junction temperature
compensation accuracy)
Example: When measuring the temperature 300

 with the input range setting

“38 (the thermocouple K, -200.0 to 400.0, in 0.1

 unit)” at ambient

temperature of 35

, the accuracy is: (400.0-(-200.0))[full scale] 

(

0.007)[

0.7%] + (

0.1

)[

1 digit] + (

1.0

)[cold-junction

temperature compensation accuracy] = 

5.3

*2: “

1 digit” error depends on the input range.

For setting unit of 1

1

   For setting unit of 0.1

0.1

*3: Only the URD International, Ltd. current sensor can be used.

Sales channels for current sensors manufactures by URD International Ltd. are
listed as follows:

U.S.A.

Julia Industries Inc.
Tel:949-831-0111

BRAZIL

Ananda Industial Ltda.
Tel:011-5584-0959

UNITED
KINGDOM Omni Components

Tel:024-7622-5757

GERMANY Allied Electronics GmbH

Tel:0221-497-3084

FRANCE

Diltronic S.A.
Tel:01-34-51-33-00

ITALY

ELNET s.n.c.
Tel:041-50-19-939

KOREA

Joyang Trading Co.
Tel:02-521-2294
Sewon Tech Co.,Ltd.
Tel:02-868-9355/9356
Keum Ho Corporation
Tel:51-319-4155/4156

HONG-KONG Weltronics Components Ltd.

Tel:2410-0623

TAIWAN

Tope Co.,Ltd.
Tel:886-2-8228-0658

INDIA

AmtechElectronics PVT.Ltd.
Tel:02712-25324

Table 2.2 The types of supported thermocouples and the measured
temperature range

°

F

Thermocouple

Measured

temperature

range

Data

resolution

Measured

temperature

range

Data

resolution

R

0 to 1700

1

0 to 3000

1

0 to 500
0 to 800

0 to 1300

1

0 to 1000
0 to 2400

1

K

-200.0 to 400.0

0.0 to 400.0
0.0 to 500.0
0.0 to 800.0

0.1

0.0 to 1000.0

0.1

0 to 500
0 to 800

0 to 1200

1

0 to 1000
0 to 1600
0 to 2100

1

J

0.0 to 400.0
0.0 to 500.0
0.0 to 800.0

0.1

0.0 to 1000.0

0.1

-200 to 400
-200 to 200

0 to 200
0 to 400

1

0 to 700

-300 to 400

1

T

-200.0 to 400.0

0.0 to 400.0

0.1

0.0 to 700.0

0.1

S

0 to 1700

1

0 to 3000

1

B

0 to 1800

1

0 to 3000

1

0 to 400

0 to 1000

1

0 to 1800

1

E

0.0 to 700.0

0.1

-

-

N

0 to 1300

1

0 to 2300

1

0 to 400

-200 to 200

1

0 to 700

-300 to 400

1

U

0.0 to 600.0

0.1

-

-

0 to 400
0 to 900

1

0 to 800

0 to 1600

1

L

0.0 to 400.0
0.0 to 900.0

0.1

-

-

PL 

0 to 1200

1

0 to 2300

1

W5Re/W26Re

0 to 2300

1

0 to 3000

1

For the general specifications, refer to the User’s Manual for the PC CPU used.

All manuals and user guides at all-guides.com

Summary of Contents for A1S64TCTT-S1

Page 1: ... ground of Type III or above Not doing so could result in malfunction z When wiring in the PC be sure that it is done correctly by checking the product s rated voltage and the terminal layout Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or failure z Tighten the terminal screws with specified torque Loose terminal screws may caus...

Page 2: ... to 255 Table 2 1 A1S64TC performance specification continued Specification Item A1S64TCTT S1 A1S64TCTTBW S1 I O occupied points 32 points Connection terminal 20 points terminal block Supported cable size 0 75 to 1 5mm Supported solderless terminal R1 25 3 1 25 YS3 RAV1 25 3 V1 25 YS3A Internal consumed current mA 330 420 Weight kg lb 0 27 0 59 0 3 0 66 External dimensions mm inch 130 5 12 H 34 5 ...

Page 3: ...r from the top of the module Remove any foreign matter from the module 4 Tighten the module installation screws within the following tightening torque range Screw position Tightening torque range Module installation screw M4 screw 78 to 118N cm Terminal block terminal screw M3 5 screw 59 to 88N cm Terminal block installation screw M4 screw 78 to 118N cm Wire breakage detection connector installati...

Page 4: ...e Assessoria Tecnica Ltda Av Rio Branco 123 15 and S 1507 Rio de Janeiro RJ CEP 20040 005 Brazil Tel 55 21 221 8343 Germany Mitsubishi Electric Europe B V German Branch Gothaer Strasse 8 D 40880 Ratingen GERMANY Tel 49 2102 486 0 U K Mitsubishi Electric Europe B V UK Branch Travellers Lane Hatfield Herts AL10 8XB UK Tel 44 1707 276100 Italy Mitsubishi Electric Europe B V Italian Branch Centro Dir ...