(N) Operation via communication and its settings
584
5.15.7
USB device communication
Changed setting value becomes valid at power ON or the inverter reset.
USB communication specifications
• At the initial setting (
Pr.551 PU mode operation command source selection
= "9999"), communication with FR
Configurator2 can be made in the PU operation mode simply by connecting a USB cable. To fix the command source to the
USB connector in the PU operation mode, set "3" in
Pr.551
.
• Parameter setting and monitoring can be performed by using FR Configurator2. For details, refer to the Instruction Manual
of FR Configurator2.
Parameters referred to
Pr.551 PU mode operation command source selection
A personal computer and an inverter can be connected with a USB cable. Setup of the inverter can be easily performed
with FR Configurator2.
The inverter can be connected simply to a personal computer by a USB cable.
Pr.
Name
Initial
value
Setting
range
Description
547
N040
USB communication
station number
0
0 to 31
Inverter station number specification
548
N041
USB communication
check time interval
9999
0
USB communication is possible, however the inverter will
trip (E.USB) when the mode changes to the PU operation
mode.
0.1 to 999.8 s
Set the communication check time interval.
If a no-communication state persists for longer than the
permissible time, the inverter will trip (E.USB).
9999
No communication check
Interface
Conforms to USB1.1 (USB2.0 full speed)
Transmission speed
12 Mbps
Wiring length
Maximum 5 m
Connector
USB mini B connector (receptacle)
Power supply
Self-powered
Recommended USB cable
MR-J3USBCBL3M (cable length 3 m)
USB cable
USB connector