(N) Operation via communication and its settings
565
5
GROUP
N
Refer to
for data formats (A, A1, A2, B, C, C1, D, E, E1, E2, E3, F)
Turning OFF the power supply while clearing parameters with H5A5A or H55AA returns the communication parameter settings to the initial
settings.
Refer to the calibration parameter list below for details on calibration parameters.
The gain frequency can be also written using
Pr.125
(instruction code: H99) or
Pr.126
(instruction code: H9A).
Inverter reset
Write
HFD
H9696: Inverter reset
• As the inverter is reset at the start of communication by the computer, the
inverter cannot send reply data back to the computer.
4 digits
(A and C/D)
H9966: Inverter reset
• After the computer correctly starts communication and send data to the
inverter, the inverter returns the ACK signal to the computer before being
reset.
4 digits
(A and D)
Fault history clear
Write
HF4
H9696: Fault history is cleared.
4 digits
(A and C/D)
Parameter clear
All clear
Write
HFC
All parameters return to initial values.
Whether to clear communication parameters or not can be selected
according to the data.
• Parameter clear
H9696: Parameters including communication parameters are cleared.
H5A5A: Parameters other than communication parameters are cleared.
• All parameter clear
H9966: Parameters including communication parameters are cleared.
H55AA: Parameters other than communication parameters are cleared.
For the details of whether or not to clear parameters, refer to
When a clear is performed with H9696 or H9966, communication related
parameter settings also return to the initial values. When resuming the
operation, set the parameters again.
Performing a clear will clear the instruction code HEC, HF3, and HFF
settings.
Only H9966 and H55AA (all parameter clear) are valid during the password
lock (refer to
4 digits
(A and C/D)
Parameter
Read
H00 to H63
Refer to the instruction code (
) and write and/or read parameter
values as required.
When setting
Pr.100
and later, the link parameter extended setting must be
set.
4 digits
(B and E/D)
Write
H80 to HE3
4 digits
(A and C/D)
Link parameter
Extended setting
Read
H7F
Parameter settings are changed (extended) according to the settings.
For details of the settings, refer to the instruction code (
).
2 digits
(B and E1/D)
Write
HFF
2 digits
(A1 and C/D)
Second parameter
changing
(instruction code
HFF = 1, 9)
Read
H6C
When setting the calibration parameters
H00: Frequency
H01: Parameter-set analog value
H02: Analog value input from terminal
2 digits
(B and E1/D)
Write
HEC
2 digits
(A1 and C/D)
Multi command
Write/
Read
HF0
Available for writing 2 commands, and monitoring 2 items for reading data
(refer to
for detail)
10 digits
(A2 and C1/
D)
Inverter
model mo
nitor
Inverter
model
Read
H7C
Reading inverter model in ASCII code.
"H20" (blank code) is set for blank area
Example of "FR-A860-1"
H46, H52, H2D, H41, H38, H36, H30, H2D, H31, H20, H20 ......... H20
20 digits
(B and E3/D)
Capacity
Read
H7D
The capacity in the inverter model can be read in ASCII code.
Data is read in increments of 0.1 kW, and rounds down to 0.01 kW
increments
"H20" (blank code) is set for blank area
Example
0.75K......... "7" (H20, H20, H20, H20, H20, H37)
6 digits
(B and E2/D)
Item
Read/
Write
Instruction
code
Data description
Number of
data digits
(Format)