(N) Operation via communication and its settings
551
5
GROUP
N
Waiting time setting from the communication line error occurrence to the
communication error activation (Pr.500)
• When a communication option is used, use
Pr.500 Communication error execution waiting time
to set the time from
when the communication line error occurs until the inverter starts the operation for the communication error.
• When a communication line error occurs and lasts longer than the time set in
Pr.500
, it is recognized as a communication
error. If the communication returns to normal within the time, it is not recognized as a communication error, and the
operation continues.
• Operation from the error occurrence until the
Pr.500
setting time elapses
When the communication returns to normal within the time period set in
Pr.500
, the protective function (E.OP1) is not activated.
Displaying and clearing the communication error count (Pr.501)
• When a communication option is used, the cumulative count of communication error occurrences can be displayed. Write
"0" to clear this cumulative count.
• When a communication line error occurs, the setting of
Pr.501 Communication error occurrence count display
increases by one.
• The cumulative count of communication error occurrences is counted from 0 to 65535. When the count exceeds 65535, the
displayed value is cleared and the counting starts over from 0 again.
NOTE
• Communication error count is temporarily stored in the RAM memory. The error count is stored in EEPROM only once per
hour. If power reset or inverter reset is performed,
Pr.501
setting will be the one that is last stored to EEPROM depending on
the reset timing.
Error reset operation selection at inverter fault (Pr.349)
• An error reset command from a communication option can be invalidated in the External operation mode or the PU
operation mode.
Fault type
Pr.502
setting
Operation
Indication
Fault output
Communication line
0
Operation
continues.
Normal
Not provided.
1
2
3
4
Communication option
0, 3
Output shutoff
"E. 1"
Output
1, 2
Output to decelerate
and stop the motor.
"E. 1" after stop
Output after stop
4
Operation continues.
"CF" warning
Not output
Pr.349 setting
Description
0 (initial value)
Error reset is enabled independently of operation mode.
1
Error reset is enabled in the Network operation mode.
100, 101
.
Normal
Error
Pr.500
setting time
Normal
Error
Communication line status
Alarm signal(LF)
(
Pr.502
= 3)
Recognition
ON
Pr.500
setting time
Communication error
(E.OP1)
Normal
Error
Count timing depending on
communication line status
Incremented by 1
Normal
Error
Incremented by 1