Control circuit
54
2.6.6
When supplying 24 V external power to the
control circuit
Connect a 24 V external power supply across ter24 and SD. Connecting a 24 V external power supply enables I/O
terminal ON/OFF operation, operation panel displays, control functions, and communication during communication operation
even at power-OFF of inverter's main circuit power supply. When the main circuit power supply is turned ON, the power
supply source changes from the 24 V external power supply to the main circuit power supply.
Specification of the applicable 24 V external power supply
Commercially available products (as of February 2015)
For the latest information about OMRON power supply, contact OMRON corporation.
Starting and stopping the 24 V external power supply operation
• Supplying 24 V external power while the main circuit power is OFF starts the 24 V external power supply operation.
Likewise, turning OFF the main circuit power while supplying 24 V external power starts the 24 V external power supply
operation.
• Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation.
NOTE
• When the 24 V external power is supplied while the main circuit power supply is OFF, the inverter operation is disabled.
• In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is
performed in the inverter, then the power supply changes to the main circuit power supply. (The reset can be disabled using
Pr.30
. (Refer to
.))
Confirming the 24 V external power supply input
• During the 24 V external power supply operation, the alarm lamp flickers.
• During the 24 V external power supply operation, the 24 V external power supply operation signal (EV) is output. To use the
EV signal, set "68 (positive logic) or 168 (negative logic)" in one of
Pr.190 to Pr.196 (Output terminal function selection)
to assign function to an output terminal.
Item
Rated specification
Input voltage
23 to 25.5 VDC
Input current
1.4 A or less
Model
Manufacturer
S8JX-N05024C
Specifications: Capacity 50 W, output voltage (DC) 24 V, output current 2.1 A
Installation method: Front installation with cover
or
S8VS-06024
Specifications: Capacity 60W, output voltage (DC) 24 V, output current 2.5 A
Installation method: DIN rail installation
OMRON Corporation
POWER ALARM