Peripheral devices
20
2.1.2
Peripheral devices
Check the model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.
Refer to the table below to prepare appropriate peripheral devices.
NOTE
• When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cables and reactors according to the motor output.
• When the breaker on the inverter's input side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter etc. The cause of the trip must be identified and removed before turning ON the power of the breaker.
Motor Output
Applicable Inverter Type
Rated current of
Molded Case Circuit Breaker
or Earth Leakage Circuit Breaker
Magnetic
Contactor
Standard
With power factor
improving reactor
0.75
FR-A860-00027
5 A
3 A
3 A
2.2
FR-A860-00061
15 A
10 A
7 A
3.7
FR-A860-00090
20 A
10 A
11 A
7.5
FR-A860-00170
30 A
20 A
19 A
15
FR-A860-00320
60 A
40 A
33 A
22
FR-A860-00450
100 A
60 A
47 A
37
FR-A860-00680
125 A
100 A
70 A
55
FR-A860-01080
175 A
125 A
99 A
75
FR-A860-01440
—
175 A
98 A
90
FR-A860-01670
—
225 A
127 A
110
FR-A860-02430
—
250 A
146 A
132
FR-A860-02890
—
350 A
192 A
185
FR-A860-03360
—
400 A
234 A
220
FR-A860-04420
—
600 A
282 A
Assumes the use of a 4-pole standard motor with the power supply voltage of 575 VAC 50 Hz.
Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the Instruction
Manual (Startup) or Instruction Manual (Hardware), and select an appropriate fuse or molded case circuit
breaker (MCCB).
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM 1038-AC-3 class rated
current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor,
select an MC regarding the rated motor current as JEM 1038-AC-3 class rated current.
MCCB
INV
MCCB
INV
M
M