333
List of fault or alarm display
5
5.2 List of fault or alarm display
* If an error occurs when using the FR-PU04, "Fault 14" is displayed on
the FR-PU04.
...
Specifications differ according to the date assembled.
to check the SERIAL number.
Operation Panel
Indication
Name
fault
Data
code
Refer
to
E
rro
r m
es
sa
ge
E---
Faults history
-
HOLD Operation panel lock
-
LOCd
Password locked
-
Er1 to 4 Parameter write error
-
rE1 to 4 Copy operation error
-
Err.
Error
-
Wa
rn
in
gs
OL
Stall prevention
(overcurrent)
-
oL
Stall prevention
(overvoltage)
-
RB
Regenerative brake
prealarm
-
TH
Electronic thermal
relay function prealarm
-
PS
PU stop
-
MT
Maintenance signal
output
-
CP
Parameter copy
-
Ala
rm
FN
Fan alarm
-
Fa
ult
E.OC1 Overcurrent trip during
acceleration
16
(H10)
E.OC2 Overcurrent trip during
constant speed
17
(H11)
E.OC3 Overcurrent trip during
deceleration or stop
18
(H12)
E.OV1
Regenerative
overvoltage trip during
acceleration
32
(H20)
E.OV2
Regenerative
overvoltage trip during
constant speed
33
(H21)
E.OV3
Regenerative
overvoltage trip during
deceleration or stop
34
(H22)
E.THT
Inverter overload trip
(electronic thermal
relay function)
48
(H30)
E.THM
Motor overload trip
(electronic thermal
relay function)
49
(H31)
E.FIN
Heatsink overheat
64
(H40)
E.IPF
Instantaneous power
failure
80
(H50)
E.UVT Undervoltage
81
(H51)
E.ILF* Input phase loss
82
(H52)
E.OLT Stall prevention stop
96
(H60)
lt
E.GF
Output side earth
(ground) fault overcurrent
128
(H80)
to
to
E.LF
Output phase loss
129
(H81)
E.OHT External thermal relay
operation *2
144
(H90)
E.PTC* PTC thermistor
operation
145
(H91)
E.OPT Option fault
160
(HA0)
E.OP1
E.OP2 Communication option
fault
161
(HA1)
162
(HA2)
E. 1
E. 2
Option fault
241
(HF1)
242
(HF2)
E.PE
Parameter storage
device fault
176
(HB0)
E.PUE PU disconnection
177
(HB1)
E.RET Retry count excess
178
(HB2)
E.PE2* Parameter storage
device fault
179
(HB3)
E. 5
E. 6
E. 7
E.CPU
CPU fault
245
(HF5)
246
(HF6)
247
(HF7)
192
(HC0)
E.CTE
Operation panel power
supply short circuit,
RS-485 terminal power
supply short circuit
193
(HC1)
E.P24 24VDC power output
short circuit
194
(HC2)
E.CDO* Output current detection
value exceeded
196
(HC4)
E.IOH* Inrush current limit
circuit fault
197
(HC5)
E.SER* Communication fault
(inverter)
198
(HC6)
E.AIE* Analog input fault
199
(HC7)
E.PID* PID signal fault
230
(HE6)
E.BE
Brake transistor alarm
detection/internal
circuit fault
112
(H70)
E.13
Internal circuit fault
253
(HFD)
E. PCH*
Pre-charge fault
229
(HE5)
E.LCI*
4mA input fault
228
(HE4)
Operation Panel
Indication
Name
fault
Data
code
Refer
to