192
Misoperation prevention and parameter
4.17.5 Password function (Pr. 296, Pr. 297)
The above parameters can be set when
Pr. 160
User group read selection
= "0".
When
Pr. 296
≠
"9999" (with password lock), note that
Pr. 297
is always available for setting regardless of
Pr. 160
setting.
* "0 or 9999" can be set to
Pr. 297
at any time although the setting is invalid (the displayed value does not change).
....
Specifications differ according to the date assembled.
to check the SERIAL number.
(1) Parameter reading/writing restriction level (
Pr. 296
)
Level of reading/writing restriction by PU/NET mode operation command can be selected by
Pr. 296
.
*1
If the parameter reading is restricted by the
Pr. 160
setting, those parameters are unavailable for reading even when " " is indicated.
*2
If the parameter writing is restricted by the
Pr. 77
setting, those parameters are unavailable for writing even when " " is indicated.
*3
Parameter access from unit where parameter is written in PU operation mode (initially set to operation panel (FR-DU07), parameter unit) is
restricted. (
for PU mode operation command source selection)
*4
This restricts parameter access from the command source that can write a parameter under Network operation mode (initially RS-485 terminal or
a communication option). (
for NET mode command source.)
*5
Read/write is enabled only in the simple mode parameters registered in the user group when
Pr.160 User group read selection
= "9999".
Pr.296
and
Pr.297
are always read/write enabled whether registered to a user group or not.
*6
If a communication option is installed, option fault (E.OPT) occurs, and inverter trips. (
Registering 4-digit password can restrict parameter reading/writing.
Parameter
Number
Name
Initial Value
Setting Range
Description
296
Password lock level
9999
0 to 6, 99, 100 to
106, 199
Select restriction level of parameter reading/
writing when a password is registered.
9999
No password lock
297
Password lock/unlock
9999
1000 to 9998
Register a 4-digit password
(0 to 5) *
Displays password unlock error count.
(Reading only)
(Valid when
Pr. 296
= "100" to "106")
9999 *
No password lock
Pr. 296
Setting
PU Mode Operation Command
NET Mode Operation Command
RS-485 Terminal
Communication Option
Read
Write
Read
Write
Read
Write
9999
0, 100
×
×
×
×
×
×
1, 101
×
×
×
2, 102
×
3, 103
×
×
4, 104
×
×
×
×
×
5, 105
×
×
6, 106
×
×
×
99, 199
Only parameters registered in the user group can be read/written.
(For the parameters not registered in the user group, same restriction level as "4, 104" applies.)
: enabled,
×
: restricted