3 AnyWireASLINK
3.5 Backing up/Restoring Data of Devices Supporting iQSS
47
3
Execution method of data restoration
The target device for data restoration can be set with a program.
■
Acquiring a right to use
Set a value within the range from 1000H to 1FFFH to SD1435.
Right to use for data backup
• Special relays (SM) and special registers (SD) are used for data restoration.
• To prevent the same special relay (SM) and special register (SD) from being set at the same time, acquiring
a right to use of them for data backup is required.
• To acquire a right to use, specify a value which is not duplicate with values for other request sources to
SD1435, and check that the value set to SD1435 is stored to SD1436.
• Normal operation cannot be assured if the data backup function is performed without confirming the
acquisition of a right to use.
■
Setting the restoration setting
1.
Setting a target module type
Set the target module type for data restoration to the lower 8 bits of SD1437.
2.
Setting an execution unit
Set the unit of execution for data restoration to the upper 8 bits of SD1437.
3.
Selecting a folder for data restoration
Set the number for backup folder name, from which data is to be restored, to SD1438.
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit in the step of 'Setting the execution unit', set the start I/O number of a
target device for data restoration to SD1439.
• Setting an ID number
When '2H' (ID unit) is set for the execution unit in the step of 'Setting the execution unit', set the ID number of a target device
for data restoration to SD1440.
*1 Specify the a 512 (200H) for an input/combined slave module.
Target module type
Description
1H: AnyWireASLINK
Set the target module type.
Execution unit
Description
1H: Module unit
Set this to specify all devices supporting iQSS which are connected to the AnyWireASLINK interface module with the
specified start I/O number.
2H: ID unit
Set this to specify only the device supporting iQSS with the specified ID number among the devices supporting iQSS
which are connected to the AnyWireASLINK interface module with the specified start I/O number.
Target folder
Description
00 to 99: Target folder specification
Specify the number among the numbers for backup folder name, 00 to 99.
Target device (Module)
Description
0 to FFH: Start I/O number
When '1H' (module unit) is set for the execution unit, set the value obtained by dividing the start I/O number of an
AnyWireASLINK master module, which is connected to a target device supporting iQSS, by 16.
Target device (ID number)
Description
0 to 255 (0FFH): Output slave
module ID number
When '2H' (ID unit) is set for the execution unit, set the ID number of a target device supporting iQSS.
512 (200H) to 767 (2FFH): Input/
combined slave module ID number
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......