2 SPECIFICATIONS
2.1 Generic Specifications
21
2
Dielectric withstand voltage test and insulation resistance test
Perform dielectric withstand voltage test and insulation resistance test at the following voltages between each terminal and
the CPU module ground terminal.
■
CPU module, I/O module
■
Expansion board, expansion adapter
For dielectric withstand voltage test and insulation resistance test of each product, refer to manuals of each product.
■
Intelligent function module
For information concerning dielectric withstand voltage and insulation resistance of intelligent function modules, refer to
manuals of each intelligent function module.
Between terminals
Dielectric
withstand voltage
Insulation resistance
Remarks
Between power supply terminal (AC power supply) and
ground terminal
1.5 kV AC for one
minute
10 M
Ω
or higher by 500 V DC
insulation resistance tester
Between power supply terminal (DC power supply) and
ground terminal
500 V AC for one
minute
Between 24 V DC service power supply connected to input
terminal (24 V DC) and ground terminal
500 V AC for one
minute
Between output terminal (relay) and ground terminal
1.5 kV AC for one
minute
Between output terminal (transistor) and ground terminal
500 V AC for one
minute
Between terminals
Dielectric
withstand voltage
Insulation resistance
Remarks
Between terminal of expansion board and ground terminal
Not allowed
Not allowed
Since the expansion board and
CPU module are not insulated, it is
not allowed to perform the
dielectric withstand voltage test
and insulation resistance test
between them.
Between terminal of expansion adapter and ground terminal
500 V AC for one
minute
10 M
Ω
or higher by 500 V DC
insulation resistance tester