62
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
Power supply check from the powered input/output module
(current consumption calculation)
If 5 V DC and 24 V DC power supplies of the CPU module are insufficient and system cannot be extended, add a powered
input/output module.
Check if power can be supplied to extension modules with the power supply capacity of the powered input/output module.
In the case of AC power supply type
Calculate following the procedure below.
1.
Check the power supply capacity of the powered input/output module.
(
Page 42 Powered input/output module)
*1 Value when 24 V DC service power supply is used for input circuits. The power supply capacity differs when external power supply is
used for input circuit.
2.
Check the current consumption of the extension module.
(
(
Page 43 Intelligent Function Module)
3.
Calculate the total current consumption of each power supply.
Type
Model
Power supply capacity
5 V DC power supply
24 V DC service power supply
Powered input/output module
FX5-32ER/ES
965 mA
250 mA
Type
Model
Current consumption
5 V DC power supply
24 V DC service power supply
Input module
FX5-16EX/ES
100 mA
85 mA
Output module
FX5-16EYR/ES
100 mA
125 mA
Simple motion modules
FX5-40SSC-S
Bus conversion module
FX5-CNV-BUS
150 mA
Analog input
FX3U-4AD
110 mA
Power supply type
Total current consumption
5 V DC power supply
460 mA
24 V DC power supply
210 mA
CPU module
Expansion
adapters
Expansion
board
Output
module
Input
module
Output
module
Input
module
FX5
Intelligent
module
FX3
Intelligent
module
Powered
input/
output
module
Power supply from powered input/output module
Bus
conversion
module
Ex.
Ex.
Ex.