background image

10

The testing should include all sensing devices, keypads, consoles, alarm indicating devices 
and any other operational devices that are part of the system.

NOTE TO USERS:

All Mircom Systems have been carefully designed to be as effective as possible. However, 
there are circumstances where they may not provide protection. Some reasons for system 
failure include the following.  The end user can minimize the occurrence of any of the following 
by proper training, testing and maintenance of the Mircom Systems: 

6.

Inadequate Testing and Maintenance.  

It is

 

imperative that the systems be periodically 

tested and subjected to preventative maintenance.  Best practices and local authority having 
jurisdiction determine the frequency and type of testing that is required at a minimum.  Mircom 
System may not function properly, and the occurrence of other system failures identified below 
may not be minimized, if the periodic testing and maintenance of Mircom Systems is not 
completed with diligence and as required.  

7.

Improper Operation.

  It is important that all system users be trained in the correct operation 

of the alarm system and that they know how to respond when the system indicates an alarm.  
A Mircom System

 

may not function as intended during an emergency situation where the user 

is unable to operate a panic or emergency switch by reason of permanent or temporary 
physical disability, inability to reach the device in time, unfamiliarity with the correct operation, 
or related circumstances.

8.

Insufficient Time.  

There may be circumstances when a Mircom System will operate as 

intended, yet the occupants will not be protected from the emergency due to their inability to 
respond to the warnings in a timely manner. If the system is monitored, the response may not 
occur in time enough to protect the occupants or their belongings.

9.

Carelessness or Safety Hazards. 

 Moreover, smoke detectors may not provide timely 

warning of fires caused by carelessness or safety hazards such as smoking in bed, violent 
explosions, escaping gas, improper storage of flammable materials, overloaded electrical 
circuits or children playing with matches or arson.

10.

Power Failure.  

Some Mircom System

 

components require adequate electrical power supply 

to operate.  Examples include: smoke detectors, beacons, HVAC, and lighting controllers.  If a 
device operates only by AC power, any interruption, however brief, will render that device 
inoperative while it does not have power.  Power interruptions of any length are often 
accompanied by voltage fluctuations which may damage Mircom Systems or other electronic 
equipment.  After a power interruption has occurred, immediately conduct a complete system 
test to ensure that the system operates as intended.

11.

Battery Failure.  

If the Mircom System or any device connected to the system operates from 

batteries it is possible for the batteries to fail. Even if the batteries have not failed, they must be 
fully charged, in good condition, and installed correctly. Some Mircom Systems use 
replaceable batteries, which have a limited life-span. The expected battery life is variable and 
in part dependent on the device environment, usage and type. Ambient conditions such as 
high humidity, high or low temperatures, or large temperature fluctuations may reduce the 
expected battery life.  Moreover, some Mircom Systems do not have a battery monitor that 
would alert the user in the event that the battery is nearing its end of life.  Regular testing and 
replacements are vital for ensuring that the batteries function as expected, whether or not a 
device has a low-battery monitor.

12.

Physical Obstructions.  

Motion sensors that are part of a Mircom System must be kept clear 

of any obstacles which impede the sensors’ ability to detect movement.  Signals being 
communicated by a Mircom System may not reach the receiver if an item (such as metal, 
water, or concrete) is placed on or near the radio path.  Deliberate jamming or other 
inadvertent radio signal interference can also negatively affect system operation.  

Summary of Contents for RAX-LCD

Page 1: ...d Wiring Manual Mircom FX 2000 Fire Control System System Normal Feb 21 2018 12 21 PM SIGNAL SILENCE FIRE DRILL SYSTEM RESET GENERAL ALARM ACKNOW LEDGE LAMP TEST ENTER TROUBLE QUEUE SUPV QUEUE ALARM QUEUE MENU CANCEL INFO MONITOR QUEUE A C ON PRE ALARM GROUND FAULT REMOTE ANNUNCIATOR ...

Page 2: ......

Page 3: ...rammable Input Switches Module 6 4 3 The RAX LCD Shared Display Chassis 6 5 0 Specifications and Features 7 5 1 Enclosure Models 7 5 2 Module Models 7 5 2 1 RAX LCD Remote FX 2000 Shared Display LCD Annunciator 7 5 2 2 RAX 1048TZDS Adder Annunciator Chassis 48 Display Points 7 5 3 Current Drain for Battery Calculations 8 5 4 Environmental Specifications 8 6 0 Warranty and Warning Information 9 ...

Page 4: ... Mechanical Assembly Diagram 2 Figure 2 Wiring Diagram 3 Figure 3 Annunciator Panel Connections 3 Table 2 Maximum Wiring Run to Last Annunciator 4 Table 3 Annunciator Address Settings 5 Figure 4 Annunciator Connections 6 Table 4 Enclosure Model Descriptions 7 ...

Page 5: ...lphanumeric LCD display that uses a simple menu system complete with a directional keypad and switches for Enter Menu Cancel and Info The display expands with up to a total of four RAX 1048TZDS Adder Annunciator or six IPS 2424DS Programmable Input Switches Modules There are five types of enclosure available the BB 1001D R BB 1002D R BB 1003D R BB 1008D R and BB 1012D R which can take 1 2 3 8 12 c...

Page 6: ... 26 5 12 75 9 95 24 9 BB 1008D R 33 0 22 5 20 9 35 2 BB 1012D R 45 0 22 5 20 9 52 0 Note The RAX 1048TZDS displays Initiating circuit status and trouble indication Indicating and relay circuits are not remotely displayed For more details see the fire alarm control panel manual that the annunciator is connected to BACKBOX CAN BE MOUNTED WITH STANDARD 4 X 4 ELECTRICAL BOXES BB 1001D R BACKBOX IS SHO...

Page 7: ...e of an appropriate gauge for the number of annunciators and the total wiring run length Use the Current Drain for Battery Calculations on page 8 to calculate the maximum current for all annunciators summed together 24 VDC INPUT 24 VDC OUTPUT 24 VDC POWER FROM FIRE ALARM CONTROL PANEL OR PREVIOUS ANNUNCIATOR 24 VDC POWER TO NEXT ANNUNCIATOR S S RS 485 INPUT RS 485 OUTPUT RS 485 TO NEXT ANNUNCIATOR...

Page 8: ... ft m Ohms 0 12 1180 360 1850 567 3000 915 4250 1296 15 0 30 470 143 750 229 1200 366 1900 579 6 0 60 235 71 375 114 600 183 850 259 3 0 90 156 47 250 76 400 122 570 174 2 1 20 118 36 185 56 300 91 425 129 1 5 1 50 94 29 150 46 240 73 343 105 1 2 1 70 78 24 125 38 200 61 285 87 1 0 SW1 1 Address A0 SW1 2 Address A1 SW1 3 Address A2 SW1 4 Address A3 SW1 5 Address A4 DIP switches are for assigning a...

Page 9: ... OFF ON OFF ON ON 53 OFF ON OFF ON OFF 38 ON OFF OFF ON ON 54 ON OFF OFF ON OFF 39 OFF OFF OFF ON ON 55 OFF OFF OFF ON OFF 40 ON ON ON OFF ON 56 ON ON ON OFF OFF 41 OFF ON ON OFF ON 57 OFF ON ON OFF OFF 42 ON OFF ON OFF ON 58 ON OFF ON OFF OFF 43 OFF OFF ON OFF ON 59 OFF OFF ON OFF OFF 44 ON ON OFF OFF ON 60 ON ON OFF OFF OFF 45 OFF ON OFF OFF ON 61 OFF ON OFF OFF OFF 46 ON OFF OFF OFF ON 62 ON OF...

Page 10: ...nects to the first RAX 1048TZDS or IPS 2424DS P2 BDM port Terminals See Wiring Instructions on page 3 for details SW1 See above for details Note The last annunciator must have 120 ohm E O L resistor connected to RS 485 output terminals P2 RAX 1048TZDS Adder Annunciator or IPS 2424DS Programmable Input Switches Module P1 POWER TERMINALS SW1 P1 RAX LCD SHARED DISPLAY BOARD RS 485 TERMINALS P2 ALARM ...

Page 11: ...or Chassis 48 Display Points Interconnect via one ribbon cable from RAX LCD or to previous RAX 1048TZDS or IPS 2424DS to the next RAX 1048TZDS or IPS 2424DS Annunciation of up to 48 additional points Standby 15 mA Max All LEDs ON 100 mA Max Table 4 Enclosure Model Descriptions Modle Number Material Description BB 1001D R 18 GA CRS Backbox for one annunciator chassis with keylock door BB 1002D R 18...

Page 12: ...mum 150 mA ___________ X 15 mA _________ X 144mA __________ number of RAX 1048TZDS number of IPS 2424DS Use the normal standby current for battery size calculations see the fire alarm control panel manual for battery calculations and includes the current drain for the Trouble Buzzer Trouble LED and one alarm LED Use the maximum current to calculate the wire size see Wiring Instructions on page 4 5...

Page 13: ... is the system a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Building automation systems produced by the Mircom Group of Companies are not to be used as a fire alarm or life safety system NOTE TO INSTALLERS All Mircom Systems have been carefully designed to be as effective as possible However there ...

Page 14: ...e timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits or children playing with matches or arson 10 Power Failure Some Mircom System components require adequate electrical power supply to operate Examples include smoke detectors beacons HVAC and lighting control...

Page 15: ...ion appliances such as sirens bells horns or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door It is less likely that the occupants will be alerted or awakened when notification appliances are located on a different level of the residence or premise 17 Software Malfunction Most Mircom Systems contain software No warranties are provided as to the software com...

Page 16: ... Tel 888 660 4655 905 660 4655 Fax 905 660 4113 Mircom 2018 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 4113 ...

Reviews: